Powered by GoogleTranslate

Inspection Detail

Inspection: 109450502 - North Houston Pole Line Corp.

Inspection Information - Office: Houston North Area Office

 

Inspection Nr: 109450502
Report ID: 0626600
Date Opened: 02/02/1993

Site Address:
North Houston Pole Line Corp.
N Eldridge/Spring Cypress
Houston, TX 77429

Mailing Address:
1608 Margaret St., Houston, TX 77093

Union Status: Union

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/04/1993

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 01/09/1995


Related Activity
Type Activity Nr Safety Health
Accident 360900831
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations
Initial Penalty $2,750 $0 $0 $0 $0 $2,750
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260950 B01 02/24/1993 03/01/1993 $2,750 $2,750 $0 03/22/1993 J - ALJ Decision Citation has been deleted.

Investigation Summary

Investigation Nr: 14240279
Event: 01/28/1993
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

A POWER LINE WORKER WAS RAISING A NO. 4/0 AWG TRIPLEX CABLE. ABOUT 2 FEET ABOVE WHERE THE TRIPLEX WAS FASTENED TO A UTILITY POLE, IT WAS FED BY A 7200-240/120-VOLT TRANSFORMER. THE EMPLOYEE REMOVED THE TRIPLEX FROM ITS BRACKET AND LAID IT ON THE EDGE OF THE BUCKET. HE HELD THE CABLE WITH ONE HAND AND RAISED THE BUCKET OF THE AERIAL LIFT HE WAS WORKING FROM WITH THE OTHER. WHEN HE DID THIS, THE NO. 4 AWG JUMPER CONNECTED TO THE TRIPLEX NEUTRAL BECAME TAUT. THE COPPER POLE GROUND HAD BEEN STOLEN FOR A LENGTH OF ABOUT 8 FEET UP FROM THE GROUND. ADDITIONALLY, THE ALUMINUM BONDING BRACKET HAD NOT BEEN CONNECTED TO THE SECONDARY NEUTRAL BUSHING ON THE TRANSFORMER. THUS, THE JUMPER WIRE WAS THE ONLY GROUND ON THE POLE. THE EMPLOYEE TOOK A PAIR OF KLEIN PLIERS AND CUT THE JUMPER APPARENTLY SO THAT HE COULD CONTINUE MOVING THE AERIAL LIFT BUCKET. THIS OPENED THE ONLY GROUND ON THE PRIMARY WINDING OF THE TRANSFORMER, AND THE EMPLOYEE WAS ELECTROCUTED.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 109450502 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.