Powered by GoogleTranslate

Inspection Detail

Inspection: 109305821 - Georgia Power Company

Inspection Information - Office: Atlanta West Area Office

 

Inspection Nr: 109305821
Report ID: 0418200
Date Opened: 06/24/1996

Site Address:
Georgia Power Company
Browns Mill & Hamilton Blvd
Atlanta, GA 30315

Mailing Address:
P. O. Box 4545, Atlanta, GA 30302

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/17/1996

Emphasis:

Case Closed: 06/08/1999


Related Activity
Type Activity Nr Safety Health
Accident 361119613
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 1 1
Initial Penalty $15,000 $0 $0 $0 $0 $15,000
Current Penalty $7,000 $0 $0 $0 $0 $7,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100269 L02 12/19/1996 01/13/1997 $7,000 $5,000 $0 01/15/1997 F - Formal Settlement  
2. 01002 Serious 19100269 M03 II 12/19/1996 01/13/1997 $5,000 $5,000 $0 01/15/1997 F - Formal Settlement Citation has been deleted.
3. 01003A Serious 19100269 N03 12/19/1996 01/13/1997 $5,000 $5,000 $0 01/15/1997 F - Formal Settlement Citation has been deleted.
4. 01003B Serious 19100269 P04 IIIC 12/19/1996 01/13/1997 $0 $0 $0 01/15/1997 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 200200103
Event: 06/22/1996
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

A troubleman and a coordinator responded to a power outage after a severe summer thunderstorm. The two employees determined that two phases of a three-phase overhead power line to an industrial building were down. This line came off a utility pole that also carried a three-phase primary circuit. The employees saw that the cause of the problem was a broken insulator on one of the primary conductors. The broken insulator was located at the top of a utility pole alongside a road. To deenergize the power lines in the area, the employees opened switches on the primary circuit on the other side of the affected pole, but decided to work the line as if it were energized. The troubleman worked from an aerial lift to replace the insulator, while his coworker spliced the two downed conductors. The troubleman replaced the insulator and dropped the rubber insulating line hose to the ground. To reattach the power line conductors, the troubleman had to come down and move his truck to the opposite side of the pole. He saw that the coordinator had finished splicing the conductors and had attached them to a jack strap. The troubleman lowered his bucket and told the coordinator to hand him the straps so that he could get it up out of the way. As the troubleman raised his bucket, the coordinator received a call from the dispatcher. He finished this call and walked back. When he called out to the troubleman, he got no response. The troubleman had contacted a 120-volt conductor to a street light and had been electrocuted (according to the autopsy report).

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 109305821 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close