Inspection Detail
Inspection: 109060905 - Air Engineering, Inc.
Inspection Information - Office: Oklahoma City Area Office
Site Address:
Air Engineering, Inc.
Heart Of Okla. Exposition Ctr., N.E. Crnr Leo/Hwy
Shawnee, OK 74801
Mailing Address:
4339 N. Santa Fe, Oklahoma City, OK 73118
Union Status: Union
SIC:7359
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/21/1993
Emphasis:
Case Closed: 10/05/1993
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361146780 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 2 | 4 | |||
| Current Violations | 2 | 2 | 4 | |||
| Initial Penalty | $6,250 | $0 | $0 | $0 | $0 | $6,250 |
| Current Penalty | $4,250 | $0 | $0 | $0 | $0 | $4,250 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100332 B01 | 08/27/1993 | 09/29/1993 | $1,250 | $1,250 | $0 | - | ||
| 2. | 01002A | Serious | 19100333 A02 | 08/27/1993 | 09/01/1993 | $3,000 | $5,000 | $0 | I - Informal Settlement | ||
| 3. | 01002B | Serious | 19100333 B02 I | 08/27/1993 | 09/01/1993 | $0 | $0 | $0 | - | ||
| 4. | 02001 | Other | 19040002 A | 08/27/1993 | 09/29/1993 | $0 | $0 | $0 | - | ||
| 5. | 02002 | Other | 19040008 | 08/27/1993 | 09/01/1993 | $0 | $0 | $0 | - |
Investigation Summary
An electrician was replacing a 480-volt fan motor on a Borg-Warner Liquid Chiller (Model No. YCH70 46A; Serial No. 178777) at an exhibit building in an exposition center. He was working alone with the circuit energized. (He apparently decided to leave the circuit energized so that the unit would still provide cooling for the exhibition hall.) The employee contacted an energized part and was electrocuted. His employer did not have a safe work practices program. Although the employee did know how to perform the job, he had not been provided with all the equipment and training necessary to perform the work. He did have a voltage measuring device and the manufacturer's instructions for repairing and replacing the motor.
Keywords: ELECTRIC MOTOR, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 109060905 | Fatality | Electric Shock | Electricians |