Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Inspection: 109059790 - Southwest Electric Company

Inspection Information - Office: Oklahoma City

Nr: 109059790Report ID: 0627700Open Date: 07/14/1993

Southwest Electric Company
6501 S. E. 74th Street
Oklahoma City, OK 73135
Union Status: Union
SIC: 3612/Power, Distribution, and Specialty Transformers
Mailing: P.O. Box 82639, Oklahoma City, OK 73135

Inspection Type:Accident
Scope:Partial Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:07/23/1993
Planning Guide: Safety-Manufacturing Close Case:09/27/1993

Related Activity:TypeIDSafetyHealth
 Accident361146764    

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $10,500 $0 $0 $0 $0 $10,500
Current Penalty $5,250 $0 $0 $0 $0 $5,250
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001A Serious 19100147 C01 08/13/1993 09/15/1993 $1,375 $2,750 $0 I - Informal Settlement
Deleted 2. 01001B Serious 19100147 C04 II 08/13/1993 09/05/1993 $0 $0 $0 I - Informal Settlement
  3. 01002 Serious 19100147 C06 I 08/13/1993 09/15/1993 $1,375 $2,750 $0 I - Informal Settlement
  4. 01003A Serious 19100333 A 08/13/1993 08/18/1993 $2,500 $5,000 $0 I - Informal Settlement
  5. 01003B Serious 19100333 C07 08/13/1993 08/18/1993 $0 $0 $0 I - Informal Settlement
  6. 01003C Serious 19100333 C09 08/13/1993 08/18/1993 $0 $0 $0 I - Informal Settlement

Accident Investigation Summary
Summary Nr: 14241871Event: 07/13/1993Electric Shock - Direct Contact With Energized Conductor
An employee was assigned to clean the top of a 17-foot, 1-inch-high oven and to lubricate the oven's motors. The rail and runway conductors for a bridge crane were located 19.5 feet above the floor, directly over the oven. The clearance between the top of the oven and the 480-volt, three-phase runway conductors was only 29 inches. As he was descending from the top of the oven, the employee stooped to go under the rail and, with his left hand, grabbed the runway conductors to maintain his balance. He was electrocuted.
Keywords: e gi iv, electrical, electrocuted, runway conductor, lockout, unguarded live parts, untrained, work surface
Inspection Degree Nature Occupation
1 109059790 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close