Inspection: 108923889 - Texas American Food Service Corp.

Inspection Information - Office: Fort Worth Area Office

 

Inspection Nr: 108923889
Report ID: 0636900
Date Opened: 07/18/1994

Site Address:
Texas American Food Service Corp.
1301 Northpark Drive
Fort Worth, TX 76102

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:2013

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/05/1994

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 03/28/1995


Related Activity
Type Activity Nr Safety Health
Accident 360904437
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 1 4
Current Violations
Initial Penalty $13,500 $0 $0 $0 $0 $13,500
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100333 A 08/12/1994 08/18/1994 $4,500 $4,500 $0 09/02/1994 J - ALJ Decision Citation has been deleted.
2. 01002 Serious 19100333 B02 IIB 08/12/1994 08/18/1994 $4,500 $4,500 $0 09/02/1994 J - ALJ Decision Citation has been deleted.
3. 01003 Serious 19100335 A01 I 08/12/1994 08/18/1994 $4,500 $4,500 $0 09/02/1994 J - ALJ Decision Citation has been deleted.
4. 02001 Other 19100333 B02 I 08/12/1994 08/18/1994 $0 $0 $0 09/02/1994 J - ALJ Decision Citation has been deleted.

Investigation Summary

Investigation Nr: 566273
Event: 07/16/1994
ELECTRIC SHOCK - FAILURE TO LOCKOUT ELECTRIC CIRCUIT

TWO ELECTRICIANS HAD BEEN ASSIGNED TO MODIFY THE LIGHTING IN A FOOD PROCESSING PLANT. THEY WERE TO INSTALL AN ADDITIONAL FIVE LIGHTING FIXTURES AND RELOCATE FOUR OTHERS. THE WORK AREA WAS ABOVE A NEW PROCESSING AREA IN AN AUXILIARY BUILDING. THE CEILING IN THIS PART OF THE PLANT WAS CONSTRUCTED OF ALUMINUM AND WAS INSTALLED WITH A 31-INCH SEPARATION FROM THE ROOF. ALL LIGHTING FOR THE AREA WAS CONTAINED WITHIN THIS SPACE. WITH THE PRESENCE OF STRUCTURAL I-BEAMS AND JUNCTION BOXES, THE CLEARANCE WAS REDUCED TO 16 TO 17 INCHES. IT WAS DETERMINED THAT WORK WOULD PROCEDE WHILE PRODUCTION WAS UNDERWAY, AND THE CIRCUITS REMAINED ENERGIZED. THE EMPLOYEES ENTERED A 24-INCH-BY-24-INCH ACCESS WAY AND CRAWLED ABOUT 30 FEET TO THE WORK AREA. THEY WERE RELOCATING A 277-VOLT HALIDE LAMP (MODEL NO. LBS-4970) WHILE LYING ON THEIR BACKS ON THE ALUMINUM SURFACE AT A JUNCTION BOX. ONE OF THE EMPLOYEES CUT THE ENERGIZED CONDUCTOR TO THE LIGHTING FIXTURE THAT WAS TO BE RELOCATED. THE OTHER EMPLOYEE REMOVED THE WIRE NUT FROM THE CONNECTION IN ORDER TO REMOVE THE CUT CONDUCTOR. HE THEN REPLACED THE WIRE NUT. HE TOOK HIS NEEDLE NOSE PLIERS (WITH AN "INSULATED" HANDLE) AND PULLED THE CONNECTION DOWN. THE FIRST EMPLOYEE HEARD A SIGH AND ASKED IF THE OTHER EMPLOYEE WAS OKAY. WHEN HE DID NOT RECEIVE A REPLY, THE FIRST EMPLOYEE TURNED HIS HEAD AND SAW THAT THE OTHER EMPLOYEE HAD BOTH HANDS ON THE PLIERS AND THAT SMOKE WAS COMING FROM THEM. THE FIRST EMPLOYEE KICKED THE INJURED EMPLOYEE OFF THE CIRCUIT, USED THE RADIO TO CALL FOR HELP, AND INITIATED CARDIO-PULMONARY RESUSCITATION. UNFORTUNATELY, HIS RESCUE EFFORTS FAILED, AND THE INJURED EMPLOYEE DIED OF ELECTROCUTION.

Keywords: ELEC PROTECT EQUIP, LIGHTING CIRCUIT, E GI IV, ELECTRICAL, CPR, INSULATED TOOL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 108923889 Fatality Electric Shock Electrical and electronic technicians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.