Powered by GoogleTranslate

Inspection Detail

Inspection: 108904657 - Jersey Central Power & Light Co.

Inspection Information - Office: Avenel Area Office

 

Inspection Nr: 108904657
Report ID: 0213400
Date Opened: 03/08/1993

Site Address:
Jersey Central Power & Light Co.
Cottrell Rd.
Old Bridge, NJ 08857

Mailing Address:
999 Englishtown Rd., Old Bridge, NJ 08857

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/20/1993

Emphasis:

Case Closed: 12/07/1993


Related Activity
Type Activity Nr Safety Health
Accident 360945448
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $10,000 $0 $0 $0 $0 $10,000
Current Penalty $10,000 $0 $0 $0 $0 $10,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 07/21/1993 09/23/1993 $5,000 $5,000 $0 A - Amendment  
2. 01002 Serious 5A0001 07/21/1993 09/23/1993 $5,000 $5,000 $0 A - Amendment  

Investigation Summary

Investigation Nr: 14309025
Event: 03/06/1993
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

A TWO-PERSON ELECTRIC UTILITY CREW WAS ASSIGNED TO REPAIR AN OVERHEAD POWER LINE. THE CENTER PHASE CONDUCTOR OF THE 7200-VOLT, THREE-PHASE OVERHEAD LINE WAS OPEN, AND ONE END OF THIS CONDUCTOR WAS HANGING DOWN OVER A TREE ABOUT 6 FEET FROM THE GROUND. THE OTHER END OF THE CONDUCTOR WAS STILL IN A TREE. THE CREW CHIEF OPENED THE SUPPLY SIDE OF THE CENTER PHASE AND ONE OUTSIDE PHASE CONDUCTOR BY OPENING THE CORRESPONDING FUSED CUTOUTS. THE OTHER PHASE CONDUCTOR WAS LEFT ENERGIZED SINCE IT FED TWO BUILDINGS AND DID NOT EXTEND TO THE POLE WHERE THE BREAK WAS. THE CREW CHIEF TOLD THE OTHER POWER LINE WORKER TO DON HIS PERSONAL PROTECTIVE EQUIPMENT AND TO GO UP IN AN AERIAL LIFT TO REPAIR THE CONDUCTOR. THE CREW CHIEF THEN GOT SPLICING TOOLS AND A COIL OF WIRE AND WENT TO THE CONDUCTOR THAT WAS HANGING DOWN FROM THE TREE. WITHOUT USING ELECTRICAL PROTECTIVE EQUIPMENT, HE CONTACTED THE DOWNED CONDUCTOR WITH HIS RIGHT HAND AND WAS ELECTROCUTED. THE CONDUCTOR WAS ENERGIZED BY VOLTAGE BACKFEED FROM TRANSFORMERS IN THE BUILDINGS.

Keywords: VOLTAGE BACKFEED, ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, LOCKOUT, E PTD, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 108904657 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.