Powered by GoogleTranslate

Inspection Detail

Inspection: 108499732 - Tvi Abq Tech-Voc Institute

Inspection Information - Office: State Of New Mexico Environment Department Occupational Health & Safety Bureau

 

Inspection Nr: 108499732
Report ID: 0653510
Date Opened: 10/06/1989

Site Address:
Tvi Abq Tech-Voc Institute
525 Buena Vista Ne
Albuquerque, NM 87152

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:8221

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 10/10/1989

Emphasis:

Case Closed: 06/18/1990


Related Activity
Type Activity Nr Safety Health
Accident 360249080
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $1,200 $0 $0 $0 $0 $1,200
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19100303 B01 03/19/1990 03/23/1990 $0 $600 $0 03/30/1990 F - Formal Settlement  
2. 01002 Other 19100303 F 03/19/1990 03/23/1990 $0 $600 $0 03/30/1990 F - Formal Settlement  

Investigation Summary

Investigation Nr: 14301600
Event: 10/06/1989
ELECTRIC SHOCK - CONTACT WITH LIVE PARTS THRU WIRE CUTTERS

AN EMPLOYEE WAS PERFORMING AN UNAUTHORIZED ELECTRICAL DISCONNECT PROCEDURE IN A BOOTH OF THE WELDING SHOP OF A VOCATIONAL INSTITUTE. THE EMPLOYEE, WHO DID NOT HAVE ANY ELECTRICAL EXPERTISE, WAS DISCONNECTING A 480-VOLT CONDUCTOR TO TWO ARC WELDING MACHINES IN THE BOOTH (A MILLER ELECTRIC MANUFACTURING CO. AC/DC TUNGSTEN ARC WELDER, SERIAL NO. HF844660, MODEL NO. 330A/BT AND AN AIRCO AIRCOMATIC WELDING MACHINE, SERIAL NO. W4910200, MODEL NO. CV250). THE DISCONNECTS FOR THE CIRCUIT HAD NOT BEEN LABELED AS TO THEIR PURPOSE, AND THE CIRCUIT REMAINED ENERGIZED WHILE THE EMPLOYEE WAS WORKING. THE EMPLOYEE, WHO WAS USING UNINSULATED WIRE CUTTERS, CUT INTO THE ENERGIZED 480-VOLT CIRCUIT CONDUCTOR WHILE HE WAS KNEELING ON A STEEL PLATE. THE EMPLOYEE RECEIVED AN ELECTRIC SHOCK AND SUFFERED CARDIO-VASCULAR AND RESPIRATORY FAILURE. THE EMPLOYEE WAS REVIVED WITH CARDIO-PULMONARY RESUSCITATION AND WAS HOSPITALIZED FOR HIS INJURY.

Keywords: E GI IV, ELECTRICAL, CPR, ELECTRICAL WORK, LOCKOUT, ELECTRIC SHOCK, HAND TOOL, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 108499732 Hospitalized injury Electric Shock Trade and industrial teachers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.