Powered by GoogleTranslate

Inspection Detail

Inspection: 107520777 - U.S. Department Of Justice, Federal Correctional I

Inspection Information - Office: Oklahoma City Area Office

 

Inspection Nr: 107520777
Report ID: 0627700
Date Opened: 08/12/1991

Site Address:
U.S. Department Of Justice, Federal Correctional I
Hwy. 66 West
El Reno, OK 73036

Mailing Address:
P.O. Box 1000, El Reno, OK 73036

Union Status: Union

SIC:9223

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership:  

Safety/Health: Safety

Close Conference: 08/19/1991

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 05/14/1993


Related Activity
Type Activity Nr Safety Health
Accident 360154363
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 6 6
Current Violations 6 6
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100147 C01 01/31/1992 03/03/1992 $0 $0 $0 -  
2. 01002 Serious 19100147 C05 I 01/31/1992 03/03/1992 $0 $0 $0 -  
3. 01003 Serious 19100147 C07 I 01/31/1992 03/03/1992 $0 $0 $0 -  
4. 01004 Serious 19100303 F 01/31/1992 02/03/1992 $0 $0 $0 -  
5. 01005 Serious 19100333 B02 I 01/31/1992 02/26/1992 $0 $0 $0 -  
6. 01006 Serious 19100333 B02 IIA 01/31/1992 12/26/1992 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 772715
Event: 08/12/1991
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

AN INMATE ELECTRICIAN AND A STAFF ELECTRICIAN WERE REPLACING A GARBAGE DISPOSAL MOTOR. THE INMATE ELECTRICIAN WAS THE SENIOR INMATE ELECTRICIAN AND WAS WORKING IN HIS NORMAL WORK AREA--THE FOOD SERVICE FACILITY AT A FEDERAL CORRECTIONS INSTITUTION. THE INMATE ELECTRICIAN HAD OPENED WHAT HE THOUGHT WAS THE APPROPRIATE CIRCUIT BREAKER IN AN INADEQUATELY MARKED PANELBOARD. UNFORTUNATELY, THIS CIRCUIT BREAKER DID NOT DEENERGIZE THE CIRCUIT ON WHICH THE EMPLOYEE WAS WORKING. ADDITIONALLY, THE EMPLOYEE DID NOT CHECK THE CIRCUIT TO ENSURE THAT IT WAS DEENERGIZED BEFORE BEGINNING TO WORK ON IT. HE WAS ELECTROCUTED AS HE REMOVED INSULATION FROM A CONDUCTOR IN THE CONTROL BOX FOR THE MOTOR. THE EMPLOYER HAD A LOCKOUT AND TAGGING POLICY, BUT NEITHER ELECTRICIAN WAS AWARE OF IT BEFORE THE ACCIDENT. THE NEED TO CHECK CONDUCTORS FOR VOLTAGE WAS DISCUSSED AT A SAFETY MEETING ATTENDED BY THE DEAD EMPLOYEE. THE STAFF ELECTRICIAN WAS A JOURNEYMAN ELECTRICIAN, BUT HE HAD NOT WORKED IN THIS OCCUPATION FOR THE 2 YEARS PRECEDING HIS EMPLOYMENT AT THE CORRECTIONS FACILITY.

Keywords: E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 107520777 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.