Powered by GoogleTranslate

Inspection Detail

Inspection: 107410052 - Dixie Electric, Inc.

Inspection Information - Office: Lubbock Area Office

 

Inspection Nr: 107410052
Report ID: 0627400
Date Opened: 12/23/1991

Site Address:
Dixie Electric, Inc.
1601 South Slaughter
Sundown, TX 79374

Mailing Address:
P. O. Box 240, Sundown, TX 79372

Union Status: NonUnion

SIC:1389

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 12/23/1991

Emphasis:

Case Closed: 03/16/1992


Related Activity
Type Activity Nr Safety Health
Accident 360341457
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 2 2
Initial Penalty $1,050 $0 $0 $350 $0 $1,400
Current Penalty $0 $0 $0 $250 $0 $250
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19100145 C03 01/23/1992 02/04/1992 $250 $1,050 $0 I - Informal Settlement  
2. 02001 Other 19040002 A 01/23/1992 01/26/1992 $0 $350 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 14445977
Event: 12/21/1991
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

TWO EMPLOYEES WERE ASSIGNED TO REPLACE TWO 12-KILOVOLT TRANSFORMERS AT A WELL SITE. ONE OF THE EMPLOYEES, A POWER LINE WORKER AND LEAD FOREMAN, USED AN INSULATED AERIAL LIFT TO REACH THE TRANSFORMERS AND TO OPEN CUTOUTS LOCATED ABOVE THE TRANSFORMER INSULATORS. AFTER HE OPENED THE CUTOUTS, THE POWER LINE WORKER EXITED THE AERIAL LIFT, DONNED HIS CLIMBING GEAR, AND CLIMBED THE POLE. AS HE WAS REACHING OVER TO DISCONNECT THE CONDUCTORS FROM THE GLASS INSULATORS, THE POWER LINE WORKER TOUCHED THE CONDUCTOR ABOVE THE CUTOUT SWITCH AND WAS ELECTROCUTED. THE MAIN PULL SWITCH ABOVE THE CUTOUT HAD NOT BEEN OPENED, LEAVING THE CUTOUT ABOVE THE TRANSFORMER ENERGIZED.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, LOCKOUT, E PTD, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 107410052 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.