Powered by GoogleTranslate

Inspection Detail

Inspection: 106811383 - Dixie Electric, Inc.

Inspection Information - Office: Lubbock Area Office

 

Inspection Nr: 106811383
Report ID: 0627400
Date Opened: 02/01/1991

Site Address:
Dixie Electric, Inc.
6 Mi Nw Offm 1936
Odessa, TX 79763

Mailing Address:
218 S Williams, Odessa, TX 79763

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 02/01/1991

Emphasis:

Case Closed: 07/21/1991


Related Activity
Type Activity Nr Safety Health
Accident 360153852
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 1 1
Initial Penalty $880 $0 $0 $0 $0 $880
Current Penalty $320 $0 $0 $0 $0 $320
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260059 E01 06/06/1991 06/28/1991 $320 $320 $0 -  
2. 01002 Serious 19260955 E20 I 06/06/1991 06/17/1991 $560 $560 $0 I - Informal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 14493837
Event: 01/31/1991
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU AERIAL LIFT

A THREE-PERSON POWER LINE CONSTRUCTION CREW WAS WORKING ON THE LAST JOB OF THE DAY. THE CREW WAS TO INSTALL NEW HARDWARE ON A GUY. THE HARDWARE WAS TO BE INSTALLED ABOVE THE 12.47-KILOVOLT (7200-VOLT-PHASE-TO-GROUND) OVERHEAD POWER LINE. THE FOREMAN ON THE CREW AND ONE OF THE TWO POWER LINE WORKERS WERE ON THE GROUND. THE THIRD EMPLOYEE, ANOTHER POWER LINE WORKER, ASCENDED IN THE BUCKET OF AN AERIAL LIFT TO PERFORM THE WORK. WHEN THE BUCKET CLEARED THE POWER LINE, THE TWO EMPLOYEES ON THE GROUND WALKED OVER TO THE SIDE OF THE AERIAL LIFT TRUCK TO GET SOMETHING FROM A METAL BIN ON THE TRUCK. AS THE FOREMAN OPENED THE DOOR OF THE BIN WITH HIS LEFT HAND, THE UNINSULATED PORTION OF THE BOOM CONTACTED THE POWER LINE, ENERGIZING THE TRUCK AND BLOWING OUT ITS TIRES. THE FOREMAN WAS ELECTROCUTED. THE OTHER TWO EMPLOYEES WERE NOT INJURED. A TRUCK GROUND AND RUBBER INSULATING LINE HOSE WERE AVAILABLE; HOWEVER, THEY WERE NOT BEING USED.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 106811383 Fatality Electric Shock Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.