Powered by GoogleTranslate

Inspection Detail

Inspection: 106785488 - Cache Valley Electric

Inspection Information - Office: Little Rock Area Office

 

Inspection Nr: 106785488
Report ID: 0627100
Date Opened: 05/02/1988

Site Address:
Cache Valley Electric
Highway 18 E., 3 Miles
Armorel, AR 72310

Mailing Address:
P. O. Box 405, Logan, UT 84321

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/03/1988

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 06/14/1988


Related Activity
Type Activity Nr Safety Health
Accident 360411086
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $450 $0 $0 $0 $0 $450
Current Penalty $450 $0 $0 $0 $0 $450
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A01 05/18/1988 05/21/1988 $450 $450 $0 -  

Investigation Summary

Investigation Nr: 14496889
Event: 05/01/1988
ELECTRIC SHOCK - CONTACT WITH LIVE PART THRU CONDUCTOR

A FOREMAN AND THREE OTHER EMPLOYEES WERE GROUNDING A FENCE SURROUNDING A SWITCHYARD. THE EQUIPMENT IN THE SUBSTATION WAS ENERGIZED WHILE THEY PERFORMED THEIR WORK. ONE OF THE EMPLOYEES HAD CUT NUMEROUS PIECES OF NO. 2 AWG SOLID COPPER CONDUCTOR INTO 8.5-FOOT LENGTHS. HE HAD BEEN DOING THIS BY LAYING THE CONDUCTOR ON THE GROUND, ROLLING OFF THE CONDUCTOR. HE THEN ROLLED THE CONDUCTOR OVER HIS HEAD, AND THE CONDUCTOR CONTACTED A 34.5-KILOVOLT TERMINAL THAT WAS ABOUT 9 FEET ABOVE THE GROUND. NONE OF THE OTHER EMPLOYEES WITNESSED THE ACCIDENT; HOWEVER, WHEN THEY HEARD THE ARC, THEY TURNED AROUND AND SAW THE INJURED EMPLOYEE FALLING BACKWARDS WITH THE COPPER CONDUCTOR IN HIS HAND. HE HAD BEEN ELECTROCUTED.

Keywords: ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, SUBSTATION, ELEC UTILITY WORK, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 106785488 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.