Powered by GoogleTranslate

Inspection Detail

Inspection: 106552631 - Indian Refinery

Inspection Information - Office: Fairview Heights Area Office

 

Inspection Nr: 106552631
Report ID: 0524530
Date Opened: 06/13/1991

Site Address:
Indian Refinery
South 7th Street
Lawrenceville, IL 62439

Mailing Address:
P.O. Box 519, Lawrenceville, IL 62439

Union Status: NonUnion

SIC:2911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 06/14/1991

Emphasis:

Case Closed: 09/10/1991


Related Activity
Type Activity Nr Safety Health
Accident 360543995
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $5,000 $0 $0 $0 $0 $5,000
Current Penalty $5,000 $0 $0 $0 $0 $5,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100333 A01 08/13/1991 08/15/1991 $5,000 $5,000 $0 -  

Investigation Summary

Investigation Nr: 14521231
Event: 06/11/1991
ELECTRIC SHOCK - GROUND FAULT IN TRANSFORMER

TWO EMPLOYEES HAD INSTALLED A 480/120-VOLT STEP-DOWN TRANSFORMER. THE TRANSFORMER HAD BEEN INSTALLED AND WAS IN USE. HOWEVER, DURING THE INITIAL INSTALLATION, ONE OF THE TWO EMPLOYEES (EMPLOYEE #1) HAD FAILED TO ENSURE THAT A BONDING JUMPER FOR THE EQUIPMENT GROUNDING CONDUCTOR HAD BEEN CONNECTED. ADDITIONALLY, A WIRING ERROR HAD BEEN MADE--ONE OF THE CIRCUIT CONDUCTORS HAD BEEN CONNECTED TO THE GROUNDING CONDUCTOR FOR THE TRANSFORMER. THE TWO EMPLOYEES WERE NOW CONNECTING THE BONDING JUMPER. IN ATTACHING THE GROUND, THE EMPLOYEE RESPONSIBLE FOR THE ORIGINAL ERROR GRABBED THE BARE GROUNDING CONDUCTOR THAT WAS ATTACHED TO THE TRANSFORMER. THIS CONDUCTOR WAS ENERGIZED BY THE GROUND FAULT, AND THE EMPLOYEE WAS ELECTROCUTED.

Keywords: E GI V, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, GROUND FAULT, EQUIPMENT GROUNDING, TRANSFORMER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 106552631 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close