Powered by GoogleTranslate

Inspection Detail

Inspection: 106384969 - Tri-City Electrical Contractors, Inc.

Inspection Information - Office: Tampa Area Office

 

Inspection Nr: 106384969
Report ID: 0420600
Date Opened: 05/24/1991

Site Address:
Tri-City Electrical Contractors, Inc.
9400 International Drive
Orlando, FL 32819

Mailing Address:
430 West Avenue, Altamonte Springs, FL 32714

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 06/19/1991

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 08/24/1993


Related Activity
Type Activity Nr Safety Health
Accident 360798276
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations
Initial Penalty $5,000 $0 $0 $0 $0 $5,000
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A03 11/07/1991 11/11/1991 $2,500 $2,500 $0 11/29/1991 F - Formal Settlement Citation has been deleted.
2. 01002 Serious 19261053 B13 11/07/1991 11/11/1991 $2,500 $2,500 $0 11/29/1991 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 14345953
Event: 05/23/1991
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED CONDUCTOR

A FOURTH-YEAR APPRENTICE ELECTRICIAN WAS IN THE LOBBY OF A HOTEL CONNECTING TWO CEILING LIGHTS TO THE LIGHTING CIRCUIT. THE HOTEL WAS IN THE FINAL STAGES OF CONSTRUCTION. THE APPRENTICE HAD TURNED OFF THE TWO CIRCUIT BREAKERS FOR THE LIGHTING CIRCUITS AND HAD TAPED THEM IN THE OPEN POSITION. SEVERAL WEEKS EARLIER, THE SAME EMPLOYEE HAD PULLED THE CONDUCTORS FOR THE TWO CIRCUITS; BUT, BY MISTAKE, TWO CONDUCTORS FROM THE PERMANENT WIRING HAD ALSO BEEN PULLED IN THE SAME CONDUIT. THE EMPLOYEE APPARENTLY DID NOT TEST THE CONDUCTORS TO ENSURE THAT THEY WERE DEENERGIZED. HE WAS STANDING ON A 12-FOOT WOODEN STEP LADDER WORKING ON A JUNCTION BOX ABOVE THE CEILING GRID. WHEN HE WAS STRIPPING THE INSULATION FROM THE ENDS OF THE CONDUCTORS, HE TOUCHED AN ENERGIZED 277-VOLT-TO-GROUND CONDUCTOR WITH HIS RIGHT HAND AND WAS ELECTROCUTED. (HE WAS ALSO KNOCKED OFF THE LADDER. HE THEN FELL TO THE CEMENT SLAB FLOOR, LANDING ON HIS HEAD.)

Keywords: LIGHTING CIRCUIT, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 106384969 Fatality Electric Shock Electricians' apprentices
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.