Powered by GoogleTranslate

Inspection Detail

Inspection: 105720759 - Dynalectric Company

Inspection Information - Office: Va-E-Manassas (Regional Office)- Safety 0355114

 

Inspection Nr: 105720759
Report ID: 0355114
Date Opened: 09/28/1989

Site Address:
Dynalectric Company
13101 Worldgate Road
Herndon, VA 22071

Mailing Address:
22930 Shaw Road, Sterling, VA 22170

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/29/1989

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 04/05/1991


Related Activity
Type Activity Nr Safety Health
Accident 360299127
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations
Initial Penalty $560 $0 $1,400 $0 $0 $1,960
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260417 B 03/26/1990 03/30/1990 $560 $560 $0 04/15/1990 Y - State Decision Citation has been deleted.
2. 02001A Repeat 19260416 A01 03/26/1990 03/30/1990 $1,400 $1,400 $0 04/15/1990 Y - State Decision Citation has been deleted.
3. 02001B Repeat 19260416 A13 03/26/1990 03/30/1990 $0 $0 $0 04/15/1990 Y - State Decision Citation has been deleted.

Investigation Summary

Investigation Nr: 947226
Event: 09/28/1989
BURN - ELECTRICAL FAULT IN PANELBOARD

AN EMPLOYEE WAS IN THE FIRE PUMP ROOM OF A BUILDING UNDER CONSTRUCTION. THE FIRE PUMP CONTROL PANEL WAS OPEN, AND SHE WAS PUSHING A 1/8-INCH FISH TAPE INTO A 3/8-INCH CONDUIT AT THE TOP OF THE PANELBOARD IN PREPARATION FOR PULLING CONDUCTORS INTO THE PANEL. ABOUT 16 FEET AWAY, OUTSIDE THE ROOM, A COWORKER WAS STANDING AT THE OTHER END OF THE CONDUIT WAITING FOR THE END OF THE FISH TAPE TO APPEAR. THE FIRST EMPLOYEE HAD ONLY PUSHED THE FISH TAPE A SHORT WAY INTO THE CONDUIT WHEN THE TAPE CONTACTED AN ENERGIZED LUG OF A THREE-PHASE, 480-VOLT, 800-AMPERE CIRCUIT LOCATED 6 TO 8 INCHES BELOW THE CONDUIT OPENING INSIDE THE PANELBOARD. THE RESULTING ELECTRIC ARC AND FIRE INFLICTED SEVERE BURNS TO THE EMPLOYEE'S HANDS, ARMS, FACE, AND UPPER TORSO BEFORE THE FIRE COULD BE EXTINGUISHED. SHE WAS HOSPITALIZED FOR HER INJURIES. SHE HAD FAILED TO ENSURE THAT THE CIRCUIT WAS DEENERGIZED BEFORE BEGINNING HER WORK.

Keywords: BURN, CLOTHING, ELECTRIC ARC, METAL WIRE, E GI IV, ELECTRICAL, PANELBOARD, ELEC CIRC PART--MISC, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 105720759 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.