Inspection Detail
Inspection: 105602338 - Allstate Electric
Inspection Information - Office: Utah Division Of Occupational Safety And Health
Site Address:
Allstate Electric
2929 South State
Salt Lake City, UT 84115
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/10/1991
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 08/07/1991
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360288542 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 2 | 2 | ||||
Current Violations | 2 | 2 | ||||
Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Other | 10100040401 | 07/22/1991 | 08/28/1991 | $0 | $0 | $0 | - | ||
2. | 01002 | Other | 10200130101 | 07/22/1991 | 08/28/1991 | $0 | $0 | $0 | - |
Investigation Summary
AN ELECTRICIAN WAS WORKING AT A RESTAURANT. THE JOB CALLED FOR INCREASED LIGHTING FOR SOME SOFFITS. THE ELECTRICIAN TURNED ON THE EXISTING LIGHTS AND THEN OPENED A CIRCUIT BREAKER TO DEENERGIZE THE LIGHTS. WHEN HE SAW THE LIGHTS GO OUT, HE THOUGHT THAT THE CIRCUIT WAS DEENERGIZED. HOWEVER, UNKNOWN TO THE EMPLOYEE, THE CONDUIT CONTAINING THE WIRING FOR THE LIGHTS ALSO CARRIED A 240-VOLT CIRCUIT POWERING A HEATER. THE ELECTRICIAN PLACED A FIBERGLASS LADDER NEXT TO THE CONDUIT SO THAT HE COULD GET TO A JOINT IN THE CONDUIT LOCATED ABOUT 10 FEET ABOVE THE FLOOR. HE DISCONNECTED THE TWO PIECES OF CONDUIT AND, WHILE HE HELD THE CONDUIT WITH ONE HAND, CUT INTO THE ENCLOSED CONDUCTORS WITH A PAIR OF DIAGONAL WIRE CUTTERS. HE RECEIVED AN ELECTRIC SHOCK AND WAS UNABLE TO LET GO OF EITHER THE WIRE CUTTERS OR THE CONDUIT. AS THE WIRE CUTTERS GOT TOO HOT TO HOLD, THE EMPLOYEE STEPPED OFF THE LADDER TO BREAK HIS HOLD ON THE CIRCUIT. THE EMPLOYEE WAS HOSPITALIZED FOR HIS INJURIES.
Keywords: E GI IV, ELECTRICAL, CONDUIT, INSULATED TOOL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRIC SHOCK, FALL
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 105602338 | Hospitalized injury | Electric Shock | Electricians |