Inspection Detail
Inspection Information - Office: Utah | ||||
---|---|---|---|---|
Nr: 105602338 | Report ID: 0854910 | Open Date: 07/10/1991 | ||
Allstate Electric | ||||
2929 South State Salt Lake City, UT 84115 | Union Status: NonUnion | |||
SIC: 1731/Electrical Work | ||||
Inspection Type: | Accident | |||
Scope: | Complete | Advanced Notice: | N | |
Ownership: | Private | |||
Safety/Health: | Safety | Close Conference: | 07/10/1991 | |
Planning Guide: | Safety-Construction | Close Case: | 08/07/1991 | |
Related Activity: | Type | ID | Safety | Health |
Accident | 360288542 |
Violation Summary | ||||||
---|---|---|---|---|---|---|
Serious | Willful | Repeat | Other | Unclass | Total | |
Initial Violations | 2 | 2 | ||||
Current Violations | 2 | 2 | ||||
Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
FTA Amount | $0 | $0 | $0 | $0 | $0 | $0 |
Violation Items | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
# | ID | Type | Standard | Issuance | Abate | Curr$ | Init$ | Fta$ | Contest | LastEvent | |
1. | 01001 | Other | 10100040401 | 07/22/1991 | 08/28/1991 | $0 | $0 | $0 | - | ||
2. | 01002 | Other | 10200130101 | 07/22/1991 | 08/28/1991 | $0 | $0 | $0 | - |
Accident Investigation Summary | ||||||
Summary Nr: 971598 | Event: 06/24/1991 | Electric Shock & Fall - Contact With Energized Conductor | ||||
AN ELECTRICIAN WAS WORKING AT A RESTAURANT. THE JOB CALLED FOR INCREASED LIGHTING FOR SOME SOFFITS. THE ELECTRICIAN TURNED ON THE EXISTING LIGHTS AND THEN OPENED A CIRCUIT BREAKER TO DEENERGIZE THE LIGHTS. WHEN HE SAW THE LIGHTS GO OUT, HE THOUGHT THAT THE CIRCUIT WAS DEENERGIZED. HOWEVER, UNKNOWN TO THE EMPLOYEE, THE CONDUIT CONTAINING THE WIRING FOR THE LIGHTS ALSO CARRIED A 240-VOLT CIRCUIT POWERING A HEATER. THE ELECTRICIAN PLACED A FIBERGLASS LADDER NEXT TO THE CONDUIT SO THAT HE COULD GET TO A JOINT IN THE CONDUIT LOCATED ABOUT 10 FEET ABOVE THE FLOOR. HE DISCONNECTED THE TWO PIECES OF CONDUIT AND, WHILE HE HELD THE CONDUIT WITH ONE HAND, CUT INTO THE ENCLOSED CONDUCTORS WITH A PAIR OF DIAGONAL WIRE CUTTERS. HE RECEIVED AN ELECTRIC SHOCK AND WAS UNABLE TO LET GO OF EITHER THE WIRE CUTTERS OR THE CONDUIT. AS THE WIRE CUTTERS GOT TOO HOT TO HOLD, THE EMPLOYEE STEPPED OFF THE LADDER TO BREAK HIS HOLD ON THE CIRCUIT. THE EMPLOYEE WAS HOSPITALIZED FOR HIS INJURIES. | ||||||
Keywords: e gi iv, electrical, conduit, insulated tool, electrician, electrical work, lockout, electric conductor, electric shock, fall | ||||||
Inspection | Degree | Nature | Occupation | |||
---|---|---|---|---|---|---|
1 | 105602338 | Hospitalized injury | Electric Shock | Electricians |