Powered by GoogleTranslate

Inspection Detail

Inspection: 105477426 - Ina Bearing Co., Inc., Plant #4

Inspection Information - Office: Sc Department Of Labor, Licensing, And Regulation

 

Inspection Nr: 105477426
Report ID: 0454510
Date Opened: 06/22/1988

Site Address:
Ina Bearing Co., Inc., Plant #4
1298 New Cut Rd.
Spartanburg, SC 29304

Mailing Address:
P. O. Box 570, Spartanburg, SC 29304

Union Status: NonUnion

SIC:3562

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/27/1988

Emphasis:

Case Closed: 08/31/1988


Related Activity
Type Activity Nr Safety Health
Accident 360279855
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 02001 Other 19100303 G01 08/11/1988 08/16/1988 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 674952
Event: 06/21/1988
BURN - ELECTRICAL FAULT IN ELECTRICAL BOX

THE PLANT ELECTRICIAN FOR A MANUFACTURING PLANT WAS CONNECTING POWER TO A ROYAL MASTER ROLL GRINDER AT A BUS DUCT DISCONNECT BOX. THE DISCONNECT BOX WAS CONNECTED TO A 600-VOLT BUS 12 FEET ABOVE THE FLOOR. ALL THE WIRING AND CONDUIT HAD BEEN INSTALLED EXCEPT FOR THE WIRING GOING INTO THE DISCONNECT BOX. A WATER PIPE HAD BEEN INSTALLED IN FRONT OF THE DOOR OF THE BOX SO THAT ITS DOOR COULD OPEN ONLY UP TO A 45 DEGREE ANGLE. THE DISCONNECT WAS IN THE OFF POSITION, AND ALL FUSES HAD BEEN REMOVED. THE ELECTRICIAN WAS STANDING ON AN ELEVATED POWER LIFT INSTALLING THE GROUNDING CONDUCTOR TO ITS CONNECTION IN THE BOX WHEN AN ELECTRICAL EXPLOSION OCCURRED. THE ELECTRICIAN HAD APPARENTLY CAUSED A GROUND FAULT. HE RECEIVED FIRST AND SECOND DEGREE BURNS TO HIS FACE AND LEFT ARM. HE WAS HOSPITALIZED FOR HIS INJURIES.

Keywords: BURN, CLOTHING, ELECTRIC ARC, E GI III, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRICAL BOX, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 105477426 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.