Powered by GoogleTranslate

Inspection Detail

Inspection: 105456545 - Alumax Of South Carolina

Inspection Information - Office: Sc Department Of Labor, Licensing, And Regulation

 

Inspection Nr: 105456545
Report ID: 0454510
Date Opened: 06/29/1988

Site Address:
Alumax Of South Carolina
Hwy 176
Goose Creek, SC 29445

Mailing Address:
400 S. El Camino Real, San Mateo, CA 94402

Union Status: NonUnion

SIC:3334

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/29/1988

Emphasis:

Case Closed: 12/22/1988


Related Activity
Type Activity Nr Safety Health
Accident 360283709
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations
Initial Penalty $420 $0 $0 $0 $0 $420
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100303 B01 09/19/1988 09/22/1988 $420 $420 $0 09/23/1988 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 735035
Event: 06/24/1988
BURN - FAULT IN MOTOR CONTROL CENTER

TWO EMPLOYEES WERE ASSIGNED TO REMOVE A 480-VOLT SPARE SWITCHGEAR CABINET IN A MOTOR CONTROL CENTER. THE EMPLOYEES REMOVED THE FRONT COVER AND OPENED THE SWITCH ENCLOSURE DOOR. THEY VISUALLY VERIFIED THAT THERE WERE NO FUSES IN THE SWITCH, THAT THE SWITCH KNIFE BLOCKS WERE OPEN, AND THAT NO CONDUCTORS WERE CONNECTED TO THE BOTTOM OF THE SWITCH. ONE OF THE EMPLOYEES OPENED THE LOCKED ACCESS DOOR TO THE LOAD SIDE OF THE SWITCH AND VISUALLY VERIFIED THAT NOTHING WAS CONNECTED TO THE LOAD SIDE. HOWEVER, NO ELECTRICAL TEST INSTRUMENTS WERE USED TO TEST FOR THE PRESENCE OF VOLTAGE WITHIN THE SWITCHGEAR ENCLOSURE. THE TWO EMPLOYEES TOOK SCREWDRIVERS (6 INCHES LONG WITH 0.25-INCH BLADES) TO REMOVE SCREWS IN THE BACK OF THE BOX. ONE OF THEM REMOVED THE TOP RIGHT SCREW, AND THE OTHER EMPLOYEE REMOVED THE BOTTOM LEFT SCREW. A FLASH OCCURRED AS A RESULT OF AN ELECTRIC ARC. THE EMPLOYEES RECEIVED BURNS ON THEIR HEADS, HANDS, AND ARMS. THEY WERE HOSPITALIZED FOR THEIR INJURIES.

Keywords: BURN, CLOTHING, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT, SWITCHGEAR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 105456545 Hospitalized injury Electric Shock Misc. electrical & electronic equipment repairers
2 105456545 Hospitalized injury Electric Shock Misc. electrical & electronic equipment repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.