Powered by GoogleTranslate

Inspection Detail

Inspection: 105456214 - Springs Industries, Granby Mills

Inspection Information - Office: Sc Department Of Labor, Licensing, And Regulation

 

Inspection Nr: 105456214
Report ID: 0454510
Date Opened: 05/23/1988

Site Address:
Springs Industries, Granby Mills
600 Heyward St.
Columbia, SC 29201

Mailing Address:
P. O. Box 207, Columbia, SC 29202

Union Status: Union

SIC:2211

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 06/07/1988

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 12/12/1988


Related Activity
Type Activity Nr Safety Health
Accident 360110993
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $490 $0 $0 $0 $0 $490
Current Penalty $163 $0 $0 $0 $0 $163
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100303 B01 06/17/1988 06/20/1988 $163 $490 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 801787
Event: 05/22/1988
ELECTRIC SHOCK - FAILURE TO TEST FOR LOCKOUT CONDITION

AN EMPLOYEE WAS STANDING ON A METAL SCAFFOLD ON A CONCRETE FLOOR, REMOVING OLD ELECTRIC CONDUCTORS FROM A JUNCTION BOX. THERE WERE 36 CONDUCTORS IN THE BOX. THE CONDUCTORS WERE THOUGHT TO BE DEENERGIZED AND LOCKED OUT. UNFORTUNATELY, ONE 575-VOLT, 600-AMPERE CIRCUIT WAS NOT DEENERGIZED, AND THE EMPLOYEE WAS ELECTROCUTED WHEN HE CONTACTED ONE OF THE CIRCUIT CONDUCTORS. THE CONDUCTORS HAD NOT BEEN TESTED TO DETERMINE WHETHER OR NOT THEY WERE ACTUALLY DEENERGIZED.

Keywords: E GI IV, ELECTRICAL, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRICAL BOX

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 105456214 Fatality Electric Shock Misc. electrical & electronic equipment repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.