Powered by GoogleTranslate

Inspection Detail

Inspection: 105223994 - Consumers Power Inc

Inspection Information - Office: Eugene

 

Inspection Nr: 105223994
Report ID: 1054114
Date Opened: 12/17/1986

Site Address:
Consumers Power Inc
Bellhaven And Huntington Dr
Corvallis, OR 97330

Mailing Address:
Po Box 1180, Philomath, OR 97370

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/17/1986

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 04/17/1987


Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $800 $0 $0 $0 $0 $800
Current Penalty $800 $0 $0 $0 $0 $800
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 7840049 03/02/1987 01/20/1987 $400 $400 $0 -  
2. 01002 Serious 7840173 03/02/1987 01/20/1987 $400 $400 $0 -  

Investigation Summary

Investigation Nr: 14204176
Event: 12/16/1986
ELECTRIC SHOCK- DIRECT CONTACT WITH UNDERGROUND LINE

A CREW OF LINEMEN WAS ATTEMPTING TO LOCATE AN ELECTRIC FAULT IN ONE OF SEVERAL UNDERGROUND CABLES WITH A THUMPER (A FAULT LOCATOR). THEY WERE WORKING AT GROUND LEVEL WHERE THE SOURCE TRANSFORMER FED A SPLITTER HOUSED IN A SMALL CONCRETE VAULT LOCATED A FEW FEET IN FRONT OF THE TRANSFORMER. AS THEIR WORK PROGRESSED, IT BECAME EVIDENT THAT THE THUMPER WAS NOT WORKING CORRECTLY. THIS INDICATED THAT THERE WERE SEVERAL POSSIBLE TROUBLE SPOTS THAT WOULD HAVE TO BE TRACKED DOWN SYSTEMATICALLY. IT WAS DETERMINED THAT THE LEAD BETWEEN THE TRANSFORMER AND THE VAULT HAD A FAULT. THE CREW THEN SET UP A JUMPER TO BYPASS THE LEAD. THERE WERE SEVERAL TIES OFF THE SPLITTER, SO THE CREW CALLED TO DETERMINE WHAT THE COLOR CODING WOULD BE INTO THE TRANSFORMER SPLITTER. IT WAS ASSUMED THAT CERTAIN PROCEDURES HAD BEEN FOLLOWED AT THE INITIAL WIRING OF THE VAULT, SO THE LINEMEN PROCEEDED TO HOOK UP THE THUMPER TO A CABLE IN ORDER TO CHECK IT. THE THUMPER DID NOT FUNCTION PROPERLY, SO ONE WORKER WENT TO CHECK THE JUMPER CABLE. HE BELIEVED THE CLAMP TO THE FUSE LINK MIGHT BE LOOSE, SO HE GRABBED THE CABLE IN ORDER TO TIGHTEN IT. AS A RESULT, HE RECEIVED A 7200-VOLT ELECTRIC SHOCK, WHICH KNOCKED HIM TO THE GROUND. HE RETAINED CONSCIOUSNESS, BUT RECEIVED ELECTRICAL BURNS ON HIS HANDS AND SUFFERED A MILD CASE OF SHOCK. HE HAD NOT BEEN WEARING RUBBER GLOVES AS REQUIRED WITH USE OF THE THUMPER, NOR HAD ANYONE CHECKED THE TEMPORARY CABLE JUMBER TO SEE IF IT WAS ENERGIZED AFTER THE THUMPER WAS SHUT OFF. ADDITIONALLY, THE COLOR CODING OF THE VAULT TIES WAS NOT CONSISTENT WITH THAT FOR THE TIES OF THE TRANSFORMER, WHICH MEANT THEY WERE WORKING WITH A DIFFERENT TIE THAN THEY BELIEVED.

Keywords: ELECTRICAL, POWER LINE WORKER, ELECTRIC CABLE, TEST EQUIPMENT, E PTD, UNDRGRD INSTALLATION, ELEC UTILITY WORK, ELECTRIC SHOCK, UNDRGRD POWER LINE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 105223994 Hospitalized injury Electric Shock Electrical and electronic technicians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.