Powered by GoogleTranslate

Inspection Detail

Inspection: 104454558 - Washington College, Inc.

Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health

 

Inspection Nr: 104454558
Report ID: 0352410
Date Opened: 10/19/1992

Site Address:
Washington College, Inc.
Rte. 213
Chestertown, MD 21620

Mailing Address:
300 Washington Avenue, Chestertown, MD 21620

Union Status: NonUnion

SIC:8221

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/30/1992

Emphasis:

Case Closed: 05/13/1993


Related Activity
Type Activity Nr Safety Health
Accident 361545296
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $4,625 $0 $0 $0 $0 $4,625
Current Penalty $1,235 $0 $0 $0 $0 $1,235
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100303 B01 01/13/1993 01/19/1993 $1,235 $4,625 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 170066211
Event: 10/16/1992
ELECTRIC SHOCK - GROUND FAULT IN FIXTURE

AN ELECTRICIAN HAD SUSPENDED A CHANDELIER TO ILLUMINATE HIS WORK AREA, WHICH WAS BELOW A CATWALK. HE HAD SUSPENDED THE CHANDELIER BY ITS CHAIN, WRAPPING IT SEVERAL TIMES AROUND THE GUARDRAIL OF THE CATWALK AND SECURING IT WITH STRING. HE HAD PLUGGED THE FIXTURE INTO A "PIGTAIL;" AND THE PIGTAIL, IN TURN, WAS PLUGGED INTO A 120-VOLT RECEPTACLE. THE EMPLOYEE WAS USING THIS ARRANGEMENT AS A PLUG ADAPTER. FROM THE WEIGHT OF THE CHANDELIER, CONSIDERABLE STRAIN WAS TRANSMITTED TO ITS INTERNAL, SPLICED CONDUCTORS. THIS STRAIN CAUSED A BARE PORTION OF ONE OF THE CONDUCTORS TO CONTACT THE METAL PARTS OF THE FIXTURE. THE ELECTRICIAN WAS ELECTROCUTED WHEN HE CONTACTED THE FIXTURE OR THE CHAIN WHILE HE WAS STANDING ON THE GROUNDED CATWALK.

Keywords: E GI V, ELECTRICAL, ELECTROCUTED, LIGHTING FIXTURE, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRIC CONDUCTOR, EQUIPMENT APPROVAL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 104454558 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close