Powered by GoogleTranslate

Inspection Detail

Inspection: 102833910 - Flint Electric Membership Corporation

Inspection Information - Office: Atlanta East Area Office

 

Inspection Nr: 102833910
Report ID: 0418100
Date Opened: 10/05/1990

Site Address:
Flint Electric Membership Corporation
Lake Joy Road
Warner Robins, GA 31093

Mailing Address:
Marion Street, Reynolds, GA 31076

Union Status: NonUnion

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/10/1990

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 12/13/1990


Related Activity
Type Activity Nr Safety Health
Accident 360414817
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $840 $0 $0 $0 $0 $840
Current Penalty $840 $0 $0 $0 $0 $840
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 11/20/1990 11/23/1990 $420 $420 $0 -  
2. 01002 Serious 5A0001 11/20/1990 11/23/1990 $420 $420 $0 -  

Investigation Summary

Investigation Nr: 608422
Event: 10/04/1990
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

TWO EMPLOYEES WERE ASSIGNED TO RESPOND TO AN OUTAGE ON A 7200-VOLT OVERHEAD POWER LINE. WHEN THEY ARRIVED AT A SET OF POLE-MOUNTED FUSES FOR THE LINE, THEY DISCOVERED THAT A FUSE FOR ONE OF THE PHASE CONDUCTORS WAS OPEN. THE LEAD POWER LINE WORKER (EMPLOYEE #1) ASSIGNED HIS COWORKER TO REPLACE THE FUSE WHILE HE RODE ALONG THE 1.5-MILE LINE. THE LEAD WORKER WAS TO RADIO BACK IF THE LINE WAS CLEAR AND IF IT WAS SAFE TO CLOSE THE FUSE. ABOUT 10 MINUTES LATER, THE LEAD WORKER CALLED HIS COWORKER AND LET HIM KNOW THAT A TREE HAD FALLEN ON THE LINE. HE TOLD THE COWORKER TO SIT CLEAR AND THAT HE WOULD REPORT BACK. TWO OTHER EMPLOYEES CALLED THE LEAD WORKER ON THE RADIO AND ASKED IF HE NEEDED ASSISTANCE. THE LEAD WORKER REPLIED THAT HE DID. THE TWO ADDITIONAL EMPLOYEES REPORTED TO THE SITE OF THE FALLEN TREE AND BEGAN TO ASSIST. THE LEAD WORKER WENT UP IN HIS AERIAL LIFT, AT A TRANSFORMER POLE, CUT THE POWER LINE, AND DESCENDED TO THE GROUND. HE WAS WALKING TOWARD ONE OF THE OTHER TWO EMPLOYEES (EMPLOYEE #2), WHO WAS ON THE GROUND, MIDWAY BETWEEN THE TRANSFORMER POLE AND AN ADJACENT POLE. THE THIRD EMPLOYEE WAS ELEVATED IN HIS AERIAL LIFT AT THE ADJACENT POLE, REPAIRING THE LINES. THIS EMPLOYEE, WHO WAS WORKING WITHOUT RUBBER INSULATING GLOVES OR SLEEVES, CONTACTED THE ENERGIZED POWER LINE AND RECEIVED AN ELECTRIC SHOCK. THE OTHER TWO EMPLOYEES ALSO CONTACTED THE ENERGIZED LINE (ALTHOUGH THE REPORT DID NOT STATE HOW) AND RECEIVED ELECTRIC SHOCKS. EMPLOYEE #2 WAS ELECTROCUTED. EMPLOYEES #1 AND 3 WERE HOSPITALIZED FOR THEIR INJURIES.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 102833910 Hospitalized injury Electric Shock Electrical power installers and repairers
2 102833910 Fatality Electric Shock Electrical power installers and repairers
3 102833910 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close