Powered by GoogleTranslate

Inspection Detail

Inspection: 102289170 - San Carlos Irrigation Project

Inspection Information - Office: Region 09; San Francisco

 

Inspection Nr: 102289170
Report ID: 0931600
Date Opened: 07/20/1992

Site Address:
San Carlos Irrigation Project
N. Of Tonto St, Near Hwy 170
San Carlos, AZ 85550

Mailing Address:
P. O. Box 250, Coolidge, AZ 85228

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership:  

Safety/Health: Safety

Close Conference: 07/20/1992

Emphasis:

Case Closed: 11/18/1993


Related Activity
Type Activity Nr Safety Health
Accident 360150353
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 7 7
Current Violations 7 7
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260021 B02 08/28/1992 01/30/1993 $0 $0 $0 I - Informal Settlement  
2. 01001B Serious 19260955 E01 08/27/1992 09/04/1992 $0 $0 $0 -  
3. 01002 Serious 19260950 C01 08/28/1992 11/15/1992 $0 $0 $0 I - Informal Settlement  
4. 01003 Serious 19260951 A02 08/28/1992 09/04/1992 $0 $0 $0 -  
5. 01004 Serious 19260951 B01 08/28/1992 11/15/1992 $0 $0 $0 I - Informal Settlement  
6. 01005 Serious 19260955 E04 08/28/1992 09/04/1992 $0 $0 $0 -  
7. 01006 Serious 19260955 E07 08/28/1992 09/04/1992 $0 $0 $0 -  
8. 01007 Serious 19600058 08/28/1992 01/30/1993 $0 $0 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 512269
Event: 07/09/1992
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

A POWER LINE WORKER IN AN AERIAL LIFT BUCKET WAS REENERGIZING A 4160-VOLT TAP DURING A CONVERSION PROJECT. THE EMPLOYEE, WHO WAS NOT USING ELECTRICAL PROTECTIVE EQUIPMENT AND WAS NOT WEARING ANY HEAD PROTECTION, HAD THE DEENERGIZED TAP IN HIS HANDS. AN UNGUARDED 4160-VOLT OVERHEAD POWER LINE WAS NEAR HIM AS HE WAS WORKING. THE EMPLOYEE CONTACTED THE POWER LINE WITH HIS FACE WHILE HE WAS APPARENTLY IN CONTACT WITH THE NEUTRAL CONDUCTOR. HE RECEIVED AN ELECTRIC SHOCK AND WAS BURNED ON THE LEFT SIDE OF HIS FACE, ON BOTH HANDS, AND ON THE INSIDE OF HIS RIGHT ELBOW, WHERE HE HAD A GAPING HOLE. BECAUSE HE WAS NOT WEARING PERSONAL FALL PROTECTION EQUIPMENT, THE EMPLOYEE FELL FROM THE BUCKET ABOUT 25 FEET TO THE GROUND. THE EMPLOYEE DIED OF ELECTROCUTION OR FROM THE INJURIES HE SUSTAINED IN THE FALL.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, FALL, FALL PROTECTION, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 102289170 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.