Powered by GoogleTranslate

Inspection Detail

Inspection: 102275021 - Eubank Electrical Contractor

Inspection Information - Office: Oklahoma City Area Office

 

Inspection Nr: 102275021
Report ID: 0627700
Date Opened: 06/01/1988

Site Address:
Eubank Electrical Contractor
Hwy. #59 At Parker & Industrial
Poteau, OK 74953

Mailing Address:
P.O. Box 1068, Choctaw, OK 73020

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/03/1988

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 12/20/1989


Related Activity
Type Activity Nr Safety Health
Accident 360159545
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $1,200 $0 $0 $0 $0 $1,200
Current Penalty $1,200 $0 $0 $0 $0 $1,200
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260955 C03 08/25/1988 08/31/1988 $600 $600 $0 -  
2. 01002 Serious 19260955 C05 08/25/1988 08/31/1988 $600 $600 $0 -  

Investigation Summary

Investigation Nr: 774992
Event: 05/26/1988
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU CONDUCTOR

Two power line workers were installing a deenergized conductor, which was about 46 meters long, between two phase conductors of a 7200-volt overhead power line. One of the power line workers was working from the bucket of an aerial lift. The metal portion of the aerial lift boom was contacting a guy. A glove bag was attached to the metal portion of the boom by a heavy metal wire that extended over into the bucket. This placed the glove bag at ground potential. The employee in the bucket was holding the new conductor while waiting for his coworker to attach the other end. The coworker was trying to secure a 3-meter-long tail when the conductor twisted and the tail struck an energized phase conductor. The employee in the bucket, who was grounded through contact with the glove bag, received an electric shock and slumped into the bucket. The coworker lowered the injured employee to the ground and administered cardiopulmonary resuscitation. Unfortunately, the injured employee died of electrocution despite the rescue efforts. (He was pronounced dead on arrival at the hospital.)

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, CPR, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRIC CONDUCTOR, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 102275021 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.