Inspection Detail
Inspection: 101911634 - Hygrade Electric Co Ltd
Inspection Information - Office: Hi-E-Honolulu
Site Address:
Hygrade Electric Co Ltd
2365 Kaanapali Pkwy
Lahaina, HI 96761
Mailing Address:
94-133 Leokane St, Waipahu, HI 96797
Union Status: Union
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/02/1986
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 10/01/1986
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360580682 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $200 | $0 | $0 | $0 | $0 | $200 |
| Current Penalty | $200 | $0 | $0 | $0 | $0 | $200 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 1410003 D06 K | 09/11/1986 | 09/02/1986 | $200 | $200 | $0 | - |
Investigation Summary
AN EMPLOYEE WAS USING A COME-ALONG TO PULL 0.5-INCH ELECTRIC CABLES FROM CONDUITS IN THE FLOOR. THE COME-ALONG WAS BEING USED DIRECTLY BENEATH A PARTIALLY ENERGIZED PANELBOARD. THE LOWER HALF OF THE PANELBOARD HAD BEEN DEENERGIZED AND CHECKED FOR VOLTAGE BEFORE WORK WAS STARTED. HOWEVER, THE UPPER HALF OF THE PANELBOARD REMAINED ENERGIZED BY THE AUTOMATIC ACTIVATION OF ANOTHER CIRCUIT. THE COME-ALONG CONTACTED THE UPPER BUSBAR WITHIN THE PANELBOARD, CAUSING AN ELECTRICAL FAULT. THE EMPLOYEE RECEIVED AN ELECTRIC SHOCK; HE ALSO RECEIVED BURNS ON BOTH FOREARMS AND HIS STOMACH. HE WAS HOSPITALIZED FOR HIS INJURIES.
Keywords: ELEC PROTECT EQUIP, E GI IV, ELECTRICAL, BUSBAR, ELECTRICAL WORK, LOCKOUT, ELECTRIC SHOCK, ELECTRICAL FAULT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 101911634 | Hospitalized injury | Burn/Scald(Heat) | Occupation not reported |
Translate