Powered by GoogleTranslate

Inspection Detail

Inspection: 101795763 - Jerry Stacey Construction

Inspection Information - Office: Dallas Area Office

 

Inspection Nr: 101795763
Report ID: 0626300
Date Opened: 12/02/1985

Site Address:
Jerry Stacey Construction
1300 Chinaberry
Lewisville, TX 75067

Mailing Address:
1922 Big Sky, Lewisville, TX 75067

Union Status: NonUnion

SIC:1751

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/02/1986

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 12/16/1986


Related Activity
Type Activity Nr Safety Health
Accident 360642144
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 2 1 3
Initial Penalty $720 $0 $0 $0 $0 $720
Current Penalty $720 $0 $0 $0 $0 $720
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260304 F 12/16/1985 12/19/1985 $300 $300 $0 -  
2. 01002A Serious 19260400 H01 12/16/1985 12/19/1985 $420 $420 $0 -  
3. 01002B Serious 19260401 A01 12/16/1985 12/19/1985 $0 $0 $0 -  
4. 01002C Serious 19260402 C03 12/16/1985 12/19/1985 $0 $0 $0 -  
5. 02001 Other 19040008 12/16/1985 12/19/1985 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14400451
Event: 11/26/1985
ELECTRIC SHOCK - GROUND FAULT IN ELECTRIC SAW

AN EMPLOYEE WAS USING A TABLE SAW TO RIP CUT SOME 2-BY-4 STUDS. THE GROUND WAS SOAKED FROM RAIN THE PREVIOUS EVENING. THE CIRCUIT WAS RUN FROM THE POWER POLE TO A HOUSEHOLD-TYPE SWITCH ON THE SAW FRAME. BARE CONDUCTORS INSIDE THE SWITCH BOX WERE TOUCHING THE FRAME OF THE BOX. THE EMPLOYEE WAS ELECTROCUTED.

Keywords: ELECTRICAL, ELECTROCUTED, ELECTRIC SAW, E C, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRIC CONDUCTOR, ELECTRICAL BOX

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101795763 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.