Powered by GoogleTranslate

Inspection Detail

Inspection: 101619807 - Griffin And Brand Of Mcallen, Inc.

Inspection Information - Office: Corpus Christi Area Office

 

Inspection Nr: 101619807
Report ID: 0626000
Date Opened: 12/22/1987

Site Address:
Griffin And Brand Of Mcallen, Inc.
4702 North 23rd. St.
Mcallen, TX 78502

Mailing Address:
P.O. Box 1840, Mcallen, TX 78502

Union Status: NonUnion

SIC:0161

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/23/1987

Emphasis:

Case Closed: 03/31/1988


Related Activity
Type Activity Nr Safety Health
Accident 360410526
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 4 6
Current Violations 2 4 6
Initial Penalty $980 $0 $0 $0 $0 $980
Current Penalty $980 $0 $0 $0 $0 $980
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100178 M12 01/21/1988 01/24/1988 $350 $350 $0 -  
2. 01002 Serious 19100252 B04 III 01/21/1988 01/24/1988 $630 $630 $0 -  
3. 02001 Other 19101200 E01 01/21/1988 02/25/1988 $0 $0 $0 -  
4. 02002 Other 19101200 F04 II 01/21/1988 02/25/1988 $0 $0 $0 -  
5. 02003 Other 19101200 G01 01/21/1988 02/25/1988 $0 $0 $0 -  
6. 02004 Other 19101200 H 01/21/1988 02/25/1988 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14391072
Event: 12/18/1987
ELECTRIC SHOCK - GROUND FAULT IN ELECTRIC WELDER

A MAINTENANCE WELDER AND HIS HELPER WERE WORKING ON AN OVERHEAD CONVEYOR. A WOODEN PALLET HAD BEEN PLACED ON THE FORKS OF A FORKLIFT TRUCK, AND A SMALL, 240-VOLT AC-MOTOR-DRIVEN DC WELDER HAD BEEN PLACED ON THE PALLET. THE HELPER RAISED THE FORKLIFT TO LIFT THE MAINTENANCE WELDER INTO THE WORKING POSITION. THE MAINTENANCE WELDER WAS ELECTROCUTED WHEN HE SIMULTANEOUSLY CONTACTED THE FRAME OF THE ELECTRIC WELDER AND AN I-BEAM. THE EQUIPMENT GROUNDING CONDUCTOR IN THE TWIST-LOCK ATTACHMENT PLUG OF THE POWER SUPPLY CORD FOR THE ELECTRIC WELDER HAD COME LOOSE. IT APPEARED THAT THE LOOSE EQUIPMENT GROUNDING CONDUCTOR HAD CONTACTED THE CIRCUIT CONDUCTOR, ENERGIZING THE FRAME OF THE ELECTRIC WELDER.

Keywords: ELECTRICAL, E GI VII, ELECTROCUTED, WELDER, ATTACHMENT PLUG, GROUND FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101619807 Fatality Electric Shock Machinery maintenance occupations
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close