Powered by GoogleTranslate

Inspection Detail

Inspection: 101581239 - Florida Power & Light Company

Inspection Information - Office: Tampa Area Office

 

Inspection Nr: 101581239
Report ID: 0420600
Date Opened: 03/22/1988

Site Address:
Florida Power & Light Company
6100 Hawkins Rd Interstate Substation
Sarasota, FL 34321

Mailing Address:
420 Venice Byway, Venice, FL 33595

Union Status: Union

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/12/1988

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 07/13/1988


Related Activity
Type Activity Nr Safety Health
Accident 360728349

Investigation Summary

Investigation Nr: 601310
Event: 03/18/1988
ELECTRIC SHOCK & BURN - CONTACT WITH O'HEAD LINE THRU ROD

TWO EMPLOYEES WERE MOVING A 7620-VOLT OVERHEAD POWER LINE FROM A TRANSFORMER BANK TO A NEW POLE AND TRANSFORMER CLUSTER. ONE OF THE EMPLOYEES, WHO WAS WORKING FROM AN AERIAL LIFT, REMOVED SOME 59-INCH-LONG ARMOR RODS FROM EACH OF THE THREE PHASE CONDUCTORS ON THE WESTERN-MOST POLE AND PLACED THEM IN THE BUCKET OF THE AERIAL LIFT. THE ARMOR RODS PROTRUDED FROM THE EDGE OF THE BUCKET FOR ABOUT 9 TO 14 INCHES. THE SECOND EMPLOYEE TOLD THE EMPLOYEE IN THE AERIAL LIFT TO REMOVE SOME OF THE RUBBER LINE HOSE FROM THE CONDUCTORS ON THE WEST SIDE OF THE CENTER POLE. THE EMPLOYEE IN THE AERIAL LIFT MOVED THE BUCKET, REMOVED THE FURTHERMOST LINE HOSE, AND DROPPED IT INTO THE BOTTOM OF THE BUCKET. APPARENTLY, THIS HOSE FELL ONTO THE ARMOR RODS, CAUSING THEM TO MOVE AND CONTACT THE POWER LINE. THERE WAS AN ELECTRIC ARC INSIDE THE BUCKET. THE EMPLOYEE IN THE BUCKET WAS ELECTROCUTED. WHEN THE BUCKET WAS LOWERED TO THE GROUND, THE SECOND EMPLOYEE RECEIVED BURNS TO HIS HANDS AS HE TRIED TO PUT OUT THE RESULTING FIRE AND APPLY FIRST AID.

Keywords: BURN, CLOTHING, METAL WIRE, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101581239 Fatality Electric Shock Electrical power installers and repairers
2 101581239 Non Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.