Inspection: 101496966 - Lang Construction Co.

Inspection Information - Office: Austin Area Office

 

Inspection Nr: 101496966
Report ID: 0625400
Date Opened: 09/06/1989

Site Address:
Lang Construction Co.
7101 Chimney Corners
Austin, TX 78731

Mailing Address:
1101 Plymouth Street, Austin, TX 78758

Union Status: NonUnion

SIC:1761

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/07/1989

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 06/26/1990


Related Activity
Type Activity Nr Safety Health
Accident 360409676
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 1 5
Current Violations 4 1 5
Initial Penalty $480 $0 $0 $0 $0 $480
Current Penalty $360 $0 $0 $0 $0 $360
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260059 E01 10/02/1989 10/20/1989 $30 $90 $0 I - Informal Settlement  
2. 01001B Serious 19260059 G01 10/02/1989 10/30/1989 $0 $0 $0 I - Informal Settlement  
3. 01001C Serious 19260059 H 10/02/1989 10/30/1989 $0 $0 $0 I - Informal Settlement  
4. 01002 Serious 19260403 E 10/02/1989 10/10/1989 $90 $120 $0 I - Informal Settlement  
5. 01003 Serious 19260404 B01 I 10/02/1989 10/10/1989 $90 $120 $0 I - Informal Settlement  
6. 01004A Serious 19260404 F06 10/02/1989 10/10/1989 $150 $150 $0 -  
7. 01004B Serious 19260404 F07 IVC 10/02/1989 10/10/1989 $0 $0 $0 -  
8. 02001 Other 19030002 A01 10/02/1989 10/06/1989 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14397731
Event: 09/01/1989
ELECTRIC SHOCK - GROUND FAULT IN ELECTRIC SCREW GUN

AN EMPLOYEE OF A CONSTRUCTION FIRM WAS STANDING ON AN ALUMINUM LADDER USING AN UNGROUNDED ELECTRIC SCREW GUN. THE TOOL WAS CONNECTED TO PERMANENT WIRING THROUGH A FLAT, UNMARKED, THREE-WIRE EXTENSION CORD SET THAT WAS ALSO UNGROUNDED. THE TOOL WAS NOT CONNECTED TO A CIRCUIT PROTECTED BY A GROUND-FAULT CIRCUIT INTERRUPTER, AND THE EMPLOYER DID NOT HAVE AN ASSURED EQUIPMENT GROUNDING CONDUCTOR PROGRAM. EVEN THOUGH THE EMPLOYEE WAS AWARE THAT ANOTHER WORKER HAD RECEIVED AN ELECTRIC SHOCK FROM THE SCREW GUN, THE EMPLOYEE CONTINUED TO USE IT. THE EMPLOYEE WAS ELECTROCUTED BY AN APPARENT GROUND FAULT IN THE TOOL.

Keywords: E GI V, ELECTRIC SCREW GUN, ELECTRICAL, CORD SET, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101496966 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close