Powered by GoogleTranslate

Inspection Detail

Inspection: 101280006 - Georgia Power Company

Inspection Information - Office: Atlanta East Area Office

 

Inspection Nr: 101280006
Report ID: 0418100
Date Opened: 03/14/1988

Site Address:
Georgia Power Company
72 Marietta St. - Lower Wall St.
Atlanta, GA 30303

Mailing Address:
271 Maple Street, N.W., Atlanta, GA 30314

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 04/22/1988

Emphasis:

Case Closed: 04/06/1989


Related Activity
Type Activity Nr Safety Health
Accident 360711246
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $1,440 $0 $0 $0 $0 $1,440
Current Penalty $1,440 $0 $0 $0 $0 $1,440
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 06/30/1988 07/02/1988 $720 $720 $0 08/22/1988 F - Formal Settlement  
2. 01002 Serious 5A0001 07/29/1988 10/04/1988 $720 $720 $0 08/22/1988 F - Formal Settlement  

Investigation Summary

Investigation Nr: 607341
Event: 03/11/1988
ELECTRIC SHOCK - GROUND FAULT IN SUMP PUMP

AN ELECTRIC UTILITY EMPLOYEE WAS IN AN UNDERGROUND VAULT CHECKING TRANSFORMER READINGS. THE VAULT CONTAINED, AMONG OTHER THINGS, AN ELECTRIC SUMP PUMP. THE PUMP HAD BEEN INOPERATIVE FOR 5 YEARS; THE FUSES PROTECTING ITS CIRCUIT HAD OPENED. HOWEVER, BECAUSE OF THE DAMP CONDITIONS, THE ELECTRICAL POWER TO THE PUMP WAS NOT ENTIRELY INTERRUPTED, EVEN WITH THE FUSES REMOVED. A LEAD SHEATH HAD WORN THROUGH ALLOWING ONE OF THE 240-VOLT CONDUCTORS TO SHORT OUT, ENERGIZING THE FRAME OF THE PUMP AND ASSOCIATED APPARATUS. THE EMPLOYEE WAS STANDING IN 3 FEET OF WATER, WEARING HIP WADERS, WHEN HE CONTACTED THE SUMP PUMP. THE EMPLOYEE WAS NOT RETRIEVED FROM THE SPACE FOR ABOUT 1.5 HOURS. HE HAD BEEN ELECTROCUTED.

Keywords: ELECTRICAL VAULT, ELECTRICAL, ELECTROCUTED, ELECTRIC PUMP, E PTD, GROUND FAULT, EQUIPMENT GROUNDING, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101280006 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.