Powered by GoogleTranslate

Inspection Detail

Inspection: 101077220 - Industrial Neon Sign Corp.

Inspection Information - Office: Houston North Area Office

 

Inspection Nr: 101077220
Report ID: 0626600
Date Opened: 08/13/1986

Site Address:
Industrial Neon Sign Corp.
1800 Augusta
Houston, TX 77080

Mailing Address:
6223 St. Augustine, Houston, TX 77021

Union Status: NonUnion

SIC:3993

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 08/26/1986

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 11/12/1986


Related Activity
Type Activity Nr Safety Health
Accident 360689715
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $420 $0 $0 $0 $0 $420
Current Penalty $420 $0 $0 $0 $0 $420
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100304 F04 08/27/1986 08/30/1986 $420 $420 $0 -  

Investigation Summary

Investigation Nr: 14498893
Event: 08/08/1986
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

AN EMPLOYEE WAS ASSIGNED THE JOB OF REPAIRING AN ELECTRIC SIGN THAT WAS REPORTED TO HAVE A LAMP OUT. THE EMPLOYEE HAD THE POWER TO THE SIGN DISCONNECTED; THEN HE REPLACED THE BALLAST. TO SEE IF THE SIGN WAS NOW IN WORKING ORDER, HE CONNECTED AN EXTENSION CORD SET (WITH ITS GROUNDING CONDUCTOR DISABLED) INTO A 3.5-KILOWATT VEHICLE-MOUNTED ELECTRIC GENERATOR. HE CUT THE CONDUCTORS AT THE BASE OF THE SIGN AND CONNECTED THEM TO THE EXTENSION CORD CONDUCTORS. THE EMPLOYEE SAW THAT THE LAMP WAS STILL NOT WORKING AND WENT BACK UP IN HIS AERIAL LIFT. HE WAS LATER FOUND SLUMPED OVER THE AERIAL LIFT BUCKET. HE HAD BEEN ELECTROCUTED.

Keywords: E GI IV, ELECTRICAL, ELECTRIC SIGN, CORD SET, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101077220 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.