Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Inspection: 100734748 - C M T Industries

Inspection Information - Office: Dallas

Nr: 100734748Report ID: 0626300Open Date: 06/19/1987

C M T Industries
2315 E. I-30
Rockwall, TX 75087
Union Status: NonUnion
SIC: 3089/Plastics Products, Not Elsewhere Classified
Mailing: Box 361, Rockwall, TX 75087

Inspection Type:Accident
Scope:Complete Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:06/22/1987
Planning Guide: Safety-Manufacturing Close Case:06/21/1988

Related Activity:TypeIDSafetyHealth
 Accident360641765    

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 11 11
Current Violations 11 11
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Amount $0 $0 $0 $500 $0 $500

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Other 19030002 A01 11/06/1987 11/09/1987 $0 $0 $500 -
  2. 01002 Other 19040002 A 11/06/1987 11/09/1987 $0 $0 $0 -
  3. 01003 Other 19100020 D01 II 11/06/1987 11/19/1987 $0 $0 $0 -
  4. 01004 Other 19100020 G02 11/06/1987 11/19/1987 $0 $0 $0 -
  5. 01005 Other 19100106 D02 I 11/06/1987 11/19/1987 $0 $0 $0 -
  6. 01006 Other 19100212 A05 11/06/1987 11/19/1987 $0 $0 $0 -
  7. 01007 Other 19100212 B 11/06/1987 11/19/1987 $0 $0 $0 -
  8. 01008 Other 19100219 D01 11/06/1987 11/19/1987 $0 $0 $0 -
  9. 01009 Other 19100219 E03 I 11/06/1987 11/19/1987 $0 $0 $0 -
  10. 01010 Other 19101200 E01 11/06/1987 11/19/1987 $0 $0 $0 -
  11. 01011 Other 19101200 H 11/16/1987 11/19/1987 $0 $0 $0 -

Accident Investigation Summary
Summary Nr: 14466536Event: 06/12/1987Electric Shock - Direct Contact With Energized Parts
A MASTER ELECTRICIAN WAS TROUBLESHOOTING AN INJECTION MOLDING HEATING UNIT. HE WAS ASSISTED BY A COWORKER. THE COWORKER WAS STANDING BY THE MAIN POWER BREAKER BOX, ENERGIZING AND DEENERGIZING THE CIRCUIT AT THE ELECTRICIAN'S REQUEST. THE ELECTRICIAN HAD REMOVED THE ACCESS PANEL FROM THE BACK OF THE HOT WATER HEATER AND HAD A BUSBAR OUT TO TEST. HE TOLD THE COWORKER TO REENERGIZE THE CIRCUIT AND REACHED HIS LEFT HAND INTO THE OPEN AREA IN BACK OF THE UNIT. THE ELECTRICIAN, WHO WAS WEARING A METAL BRACELET ON HIS LEFT WRIST, CONTACTED AN ENERGIZED PART OF THE CIRCUIT; AND THE COWORKER SAW HIS EYES GET BIG AND HEARD HIM GRUNT. THE COWORKER IMMEDIATELY DEENERGIZED THE CIRCUIT. THE ELECTRICIAN PULLED HIS HAND OUT FROM BEHIND THE HEATING UNIT AND HELD HIS INJURED HAND IN HIS RIGHT HAND. HE THEN SAT DOWN, LOST CONSCIOUSNESS, AND LATER DIED. THE MEDICAL EXAMINER RULED THAT THE EMPLOYEE HAD BEEN ELECTROCUTED.
Keywords: electrical, e gi vi, electrocuted, electrical work, lockout, electrical box, blind reaching
Inspection Degree Nature Occupation
1 100734748 Fatality Electric Shock Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close