Powered by GoogleTranslate

Inspection Detail

Inspection: 100576735 - Icg Electric

Inspection Information - Office: Englewood Area Office

 

Inspection Nr: 100576735
Report ID: 0830600
Date Opened: 10/23/1992

Site Address:
Icg Electric
1506 N. Highlands Ranch Parkway
Highlands Ranch, CO 80126

Mailing Address:
1220 Valley Street, Colorado Springs, CO 80915

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 01/21/1993

Emphasis:

Case Closed: 04/05/1994


Related Activity
Type Activity Nr Safety Health
Referral 901210096 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 7 7
Current Violations 4 4
Initial Penalty $28,000 $0 $0 $0 $0 $28,000
Current Penalty $16,000 $0 $0 $0 $0 $16,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 02/10/1993 04/15/1993 $2,000 $4,000 $0 02/25/1993 J - ALJ Decision  
2. 01002 Serious 19260020 B01 02/10/1993 04/15/1993 $2,000 $4,000 $0 02/25/1993 J - ALJ Decision  
3. 01003 Serious 19260021 B02 02/10/1993 02/14/1993 $4,000 $4,000 $0 02/25/1993 J - ALJ Decision Citation has been deleted.
4. 01004 Serious 19260556 B02 V 02/10/1993 04/15/1993 $4,000 $4,000 $0 02/25/1993 J - ALJ Decision  
5. 01005 Serious 19260950 B01 02/10/1993 02/14/1993 $8,000 $4,000 $0 02/25/1993 J - ALJ Decision  
6. 01006 Serious 19260950 C01 02/10/1993 02/14/1993 $0 $4,000 $0 02/25/1993 J - ALJ Decision Citation has been deleted.
7. 01007 Serious 19260950 D01 02/10/1993 02/14/1993 $4,000 $4,000 $0 02/25/1993 J - ALJ Decision Citation has been deleted.

Investigation Summary

Investigation Nr: 524371
Event: 10/23/1992
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

Two employees were in an aerial lift, connecting a light that was installed next to a trailer. One of them had disconnected the jumper from the primary side of a transformer, leaving the conductor attached to the hot stick. However, he did not remove the jumper from the secondary of the transformer. When he touched the end of the disconnected jumper, he received an electric shock from voltage backfeed. He was hospitalized for his injury. (The other employee in the aerial lift was not injured.)

Keywords: VOLTAGE BACKFEED, ELEC PROTECT EQUIP, OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 100576735 Hospitalized injury Amputation Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.