Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Inspection: 100435650 - New England Power Company

Inspection Information - Office: South Boston

Nr: 100435650Report ID: 0111400Open Date: 11/25/1986

New England Power Company
24 Fort Avenue
Salem, MA 01970
Union Status: Union
SIC: 4911/Electric Services

Inspection Type:Unprog Rel
Scope:Partial Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:03/06/1987
Close Case:04/20/1987

Related Activity:TypeIDSafetyHealth
 Accident360669360    

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $480 $0 $0 $0 $0 $480
Current Penalty $480 $0 $0 $0 $0 $480
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Serious 5A0001 03/13/1987 03/16/1987 $480 $480 $0 I - Informal Settlement

Accident Investigation Summary
Summary Nr: 656801Event: 11/21/1986Electric Shock - Ground Fault In Receptacle Outlet
AN AUDIOMETRIC TESTING TRAILER WAS WITHOUT ELECTRIC POWER EVEN THOUGH THE TRAILER'S SUPPLY CORD WAS PLUGGED INTO A 480-VOLT RECEPTACLE OUTLET. (IT WAS RAINING HEAVILY AT THE TIME.) AN ELECTRICIAN, WHO WAS CHECKING ON THE PROBLEM, WENT TO SEE IF THE MAIN DISCONNECT FOR THE OUTLET WAS OPEN. WHILE THE ELECTRICIAN WAS GONE, AN AUDIOMETRIC TESTING TECHNICIAN REACHED INTO THE REEL COMPARTMENT OF THE TRAILER AND WAS ELECTROCUTED WHEN HE TOUCHED THE TRAILER FRAME. HE WAS STANDING ON A METAL TRENCH COVER AT THE TIME. FURTHER INVESTIGATION REVEALED THAT THE EQUIPMENT GROUNDING CONDUCTOR FOR THE RECEPTACLE HAD BEEN CONNECTED TO ONE OF THE CIRCUIT TERMINALS AND THAT THE CORRESPONDING CIRCUIT CONDUCTOR HAD BEEN CONNECTED TO THE EQUIPMENT GROUNDING TERMINAL. THIS CAUSED VOLTAGE TO BE IMPRESSED ON THE TRAILER FRAME, AND A VOLTAGE TEST INDICATED THAT THERE WAS 250 VOLTS BETWEEN THE TRAILER AND THE METAL TRENCH COVER. CARDIOPULMONARY RESUSCITATION WAS ATTEMPTED ON THE TECHNICIAN WITHOUT SUCCESS. THE AMOUNT OF TIME THAT HAD ELAPSED BETWEEN CONTACT AND CPR APPLICATION WAS NOT REPORTED.
Keywords: receptacle, electrical, cpr, e gi vii, ground fault, electrocuted, trailer
Inspection Degree Nature Occupation
1 100435650 Occupation Not Listed

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.