Inspection: 100379015 - Electrical Distribution Contractors Inc.

Inspection Information - Office: Tampa Area Office

 

Inspection Nr: 100379015
Report ID: 0420600
Date Opened: 10/10/1985

Site Address:
Electrical Distribution Contractors Inc.
East Of 3080 Corey Road
Malabar, FL 32950

Mailing Address:
P.O. Box Aj, Apopka, FL 32703

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/14/1985

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 01/24/1986


Related Activity
Type Activity Nr Safety Health
Accident 360710735
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $640 $0 $0 $0 $0 $640
Current Penalty $640 $0 $0 $0 $0 $640
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260955 C03 01/07/1986 01/10/1986 $640 $640 $0 -  
2. 01001B Serious 19260955 C07 III 01/07/1986 01/10/1986 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14346514
Event: 10/08/1985
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU NEW LINE

TWO EMPLOYEES WERE USING A COME-ALONG TO SAG NEWLY INSTALLED OVERHEAD POWER LINES. THEY WERE WORKING OUT OF A HYDRAULIC, ARTICULATING-BOOM-TYPE AERIAL LIFT. ONE OF THE EMPLOYEES WAS WORKING THE TAKE-UP HANDLE OF THE COME-ALONG, THE OTHER WAS HOLDING THE EXCESS CHAIN AWAY FROM THE OPERATOR'S HAND. THE SECOND EMPLOYEE APPARENTLY REACHED WITH HIS OTHER HAND AND GRASPED THE POWER LINE BEHIND HIM. THIS LINE HAD CONTACTED ONE OF THE EXISTING ENERGIZED LINES BECAUSE A SUPPORT ROPE HAD BROKEN OR SLIPPED TWO POLES NORTH OF WHERE THE EMPLOYEES WERE WORKING. NO GROUNDS HAD BEEN INSTALLED ON THE NEW LINES, EVEN THOUGH THEY CROSSED OVER AND RAN PARALLEL TO UNGUARDED, ENERGIZED OVERHEAD POWER LINES.

Keywords: ELEC PROTECT EQUIP, HAND WINCH, OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, ELECTROCUTED, E PTD, ELEC UTILITY WORK, WINCH, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 100379015 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.