Powered by GoogleTranslate

Inspection Detail

Inspection: 100267467 - Crown Central Petroleum Corp

Inspection Information - Office: Houston North Area Office

 

Inspection Nr: 100267467
Report ID: 0626600
Date Opened: 10/24/1985

Site Address:
Crown Central Petroleum Corp
111 Red Bluff
Pasadena, TX 77506

Mailing Address:
Po Box 1759, Houston, TX 77001

Union Status: Union

SIC:2911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/14/1985

Emphasis:

Case Closed: 03/24/1986


Related Activity
Type Activity Nr Safety Health
Accident 360141030
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $490 $0 $0 $0 $0 $490
Current Penalty $490 $0 $0 $0 $0 $490
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 02/13/1986 03/19/1986 $490 $490 $0 -  

Investigation Summary

Investigation Nr: 14498331
Event: 10/24/1985
EXPLOSION AND FIRE - FLAM VAPOR PRESSURE VESSEL RUPTURED

AN ALKYLATION PROCESS UNIT WAS SHUT DOWN FOR MAINTENANCE. WHILE TWO PRESSURE VESSELS CONTAINING LPG WERE BEING DEPRESSURIZED, AN EXPLOSION AND FLASH FIRE OCCURRED. THE EXPLOSION WAS CAUSED BY A PLUGGED FLARE LINE THAT LEAD TO THE OVERPRESSURIZATION OF A NEUTRALIZER DRUM AND SUBSEQUENT RUPTURE. THE FLASH FIRE WAS CAUSED BY THE IGNITION OF THE HYDROCARBONS RELEASED BY THE EXPLOSION (RUPTURE) OF THE NEUTRALIZER DRUM. THE IGNITION SOURCE WAS FOUND TO BE AN ARC BETWEEN TWO POWER LINES IN THE VICINITY OF THE UNIT. TWELVE EMPLOYEES OF THREE MAINTENANCE CONTRACTORS SUSTAINED INJURIES. SIX REQUIRED HOSPITALIZATION. TYPES OF INJURIES WERE BURNS, ABRASIONS, SPRAINS AND A FRACTURE. THE WORK BEING DONE BY THESE WORKERS HAD NO RELATION TO THE EXPLOSION OR FLASH FIRE.

Keywords: ELECTRIC ARC, ELECTRICAL, FLAMMABLE VAPORS, E GI VII, EXPLOSION, BURN, CLOTHING, FIRE, FRACTURE, MAINTENANCE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 100267467 Occupation Not Listed
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close