Accident Summary Nr: 201390945 - Six Employees Killed In Explosion

Accident Summary Nr: 201390945 -- Report ID: 0552652 -- Event Date: 02/01/1999
Inspection NrDate OpenedSICNAICSEstablishment Name
12724210502/01/199949310Ford Power & Utilities Group

Abstract: Six employees were taking a boiler off-line for maintenance. A natural gas valve was inadvertently left open. When a secondary butterfly valve was opened for purging, gas entered the unfired boiler which was still hot. This resulted in an explosion in the boiler and that explosion caused secondary explosions from coal dust that had accumulated on building and equipment surfaces. All six employees were killed in the explosion.

Keywords: HEAT, COAL DUST, BOILER, NATURAL GAS, EXPLOSION, ELEC UTILITY WORK

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 127242105 Fatality Other Occupation not reported
2 127242105 Fatality Other Occupation not reported
3 127242105 Fatality Other Occupation not reported
4 127242105 Fatality Other Occupation not reported
5 127242105 Fatality Other Occupation not reported
6 127242105 Fatality Other Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.