Inspection Detail
Inspection: 998470.015 - Conservation Services, Inc.
Inspection Information - Office: Austin Area Office
Site Address:
Conservation Services, Inc.
2504 Bowman Ave.
Austin, TX 78703
Mailing Address:
2919 Wadsworth Way, Austin, TX 78748
Union Status: NonUnion
SIC:
NAICS: 238220/ Plumbing, Heating, and Air-Conditioning Contractors
Inspection Type: Fat/Cat
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/02/2014
Emphasis: L:Constr6
Case Closed: 04/04/2016
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 912281 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 3 | 1 | 4 | |||
Current Violations | 2 | 1 | 3 | |||
Initial Penalty | $11,000 | $0 | $0 | $0 | $0 | $11,000 |
Current Penalty | $3,600 | $0 | $0 | $0 | $0 | $3,600 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19260020 B02 | 02/19/2015 | 03/10/2015 | $3,000 | $7,000 | $0 | I - Informal Settlement | ||
2. | 01002 | Serious | 19260416 E01 | 02/19/2015 | 03/10/2015 | $600 | $2,400 | $0 | I - Informal Settlement | ||
3. | 01003A | Serious | 19261053 B01 | 02/19/2015 | 03/10/2015 | $0 | $1,600 | $0 | I - Informal Settlement | Citation has been deleted. | |
4. | 01003B | Serious | 19261053 B13 | 02/19/2015 | 03/10/2015 | $0 | $0 | $0 | I - Informal Settlement | Citation has been deleted. | |
5. | 02001 | Other | 19100134 C02 I | 02/19/2015 | 03/10/2015 | $0 | $0 | $0 | I - Informal Settlement |
Investigation Summary
At approximately 2:30 p.m. on October 1, 2014, Employee #1 was installing ductwork. He crawled into a tight space where gas pipes were running across the attic floor. A junction box with faulty wiring coming into contact with metal ductwork causing a neutral current to pass through someone in contact with both the ductwork and a ground path. The employee was electrocuted when coming into contact with the gas pipes and metal ductwork carrying a neutral current. The metallic ductwork was lying across a junction box that did not have a neutral conductor. The neutral wire was tied to a bare wire that was poorly attached to the junction box. Employee #2 tried to assist in pulling Employee #1 away from the workspace and touched the gas pipes for stability, and sustained an electrical shock.
Keywords: Electric Shock, Electrical, Electrocuted, Residential Construction
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 998470.015 | 55 | M | Fatality | Construction laborers |