Powered by GoogleTranslate

Inspection Detail

Case Status: CLOSED

Inspection: 897267.015 - Service Electric Company

Inspection Information - Office: Jacksonville Area Office

 

Inspection Nr: 897267.015
Report ID: 0419700
Date Opened: 03/21/2013

Site Address:
Service Electric Company
3621 Cr 2300
Panama City, FL 32405

Mailing Address:
P.O. Box 3656 1631 E. 25th Street, Chattanooga, TN 37404

Union Status: Union

SIC:

NAICS: 238210/Electrical Contractors


Inspection Type: Fat/Cat

Scope: Complete

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 03/21/2013

Emphasis: L:Ohpwrlne

Case Closed: 05/23/2014


Related Activity
Type Activity Nr Safety Health
Accident 810206
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 1 1
Initial Penalty $14,000 $0 $0 $0 $0 $14,000
Current Penalty $7,000 $0 $0 $0 $0 $7,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260955 E02 07/10/2013 08/05/2013 $7,000 $7,000 $0 I - Informal Settlement  
2. 01001B Serious 19260955 C03 07/10/2013 08/05/2013 $0 $0 $0 I - Informal Settlement Citation has been deleted.
3. 01001C Serious 19260955 C02 07/10/2013 08/05/2013 $0 $7,000 $0 I - Informal Settlement  
4. 02001 Other 19260503 B01 07/10/2013 08/05/2013 $0 $0 $0 I - Informal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 42539.015
Event: 03/20/2013
Employee holding ungrounded wire is electricuted

At 10:30 a.m. on March 20, 2013, Employee #1 and Coworker #1, employed by an electrical contractor, were performing utility work. Employee #1, who was wearing leather gloves, was holding one end of a guy wire, and Coworker #1 was cutting the wire with a large wire cutter. The guy wire was not properly grounded from inductive energy from two overhead power wires carrying 230 KV of electrical energy. Employee #1 was electrocuted. The subsequent investigation reported what appeared to have been thermal burns to Employee #1's left hand, left forearm, and lower extremities.

Keywords: Burn, Construction, Elec Utility Work, Electrical, Electrocuted, Glove, Lockout/Tagout, PPE, Power Lines, Wire Line

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 897267.015 30 M Fatality Electrical Power-Line
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close