Powered by GoogleTranslate

Inspection Detail

Inspection: 785253 - Regulating Control Systems Inc.

Inspection Information - Office: Erie Area Office

 

Inspection Nr: 785253
Report ID: 0336000
Date Opened: 08/15/1989

Site Address:
Regulating Control Systems Inc.
Sharon Steel Broadway & Roemer Street
Farrell, PA 16121

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/15/1989

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 10/19/1989


Related Activity
Type Activity Nr Safety Health
Accident 360729941
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $640 $0 $0 $0 $0 $640
Current Penalty $640 $0 $0 $0 $0 $640
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260021 B02 09/29/1989 10/18/1989 $640 $640 $0 -  
2. 01001B Serious 19260416 A01 09/29/1989 10/18/1989 $0 $0 $0 -  
3. 01001C Serious 19260416 A03 09/29/1989 10/18/1989 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14243927
Event: 08/11/1989
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

AN EMPLOYEE WAS TESTING ENERGIZED ELECTRIC CIRCUITS IN AN ELECTRICAL CABINET. THE EMPLOYEE WAS NOT USING ELECTRICAL PROTECTIVE EQUIPMENT AS THE USE OF PROTECTIVE EQUIPMENT WAS NOT REQUIRED BY HIS EMPLOYER. OF SIX CIRCUITS TO BE INSPECTED, FIVE HAD BEEN COMPLETED, AND THE LAST WAS BEING TESTED. THE FIVE PREVIOUSLY TESTED CIRCUITS WERE TURNED "OFF". HOWEVER, BECAUSE OF A WIRING ERROR, THE FIFTH CIRCUIT WAS ENERGIZED WHILE THE SIXTH CIRCUIT WAS ENERGIZED. THE EMPLOYEE ASSUMED THAT THE FIFTH CIRCUIT WAS DEENERGIZED, BUT HE HAD ONLY TESTED THE FIRST TWO OF THE DEENERGIZED CIRCUITS TO ENSURE THAT THEY WERE IN FACT DEENERGIZED. WHILE HE WAS TESTING THE LAST CIRCUIT, HE ACCIDENTALLY CONTACTED THE FIFTH CIRCUIT AND WAS ELECTROCUTED.

Keywords: E GI II, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, PANELBOARD, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 785253 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close