Inspection Detail
Inspection: 781526 - Corsicana Field Fund
Inspection Information - Office: Dallas Area Office
Site Address:
Corsicana Field Fund
Garvin Substation
Corsicana, TX 75110
Mailing Address:
P O Box 1598, Corsicana, TX 75110
Union Status: NonUnion
SIC:1389
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 03/13/1985
Emphasis: L:Oilgas
Case Closed: 10/01/1986
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360639983 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $350 | $0 | $0 | $0 | $0 | $350 |
| Current Penalty | $350 | $0 | $0 | $0 | $0 | $350 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 19100304 F04 | 03/19/1985 | 04/12/1985 | $350 | $350 | $0 | - | ||
| 2. | 01001B | Serious | 19100305 B01 | 03/19/1985 | 04/12/1985 | $0 | $0 | $0 | - | ||
| 3. | 01001C | Serious | 19100305 E01 | 03/19/1985 | 04/12/1985 | $0 | $0 | $0 | - |
Investigation Summary
AN EMPLOYEE WAS CHECKING THE FUSES IN A DISCONNECT BOX THAT WAS INSTALLED OUTDOORS. AN ENERGIZED UNGROUNDED CIRCUIT CONDUCTOR WAS IN CONTACT WITH THE SIDE OF THE BOX, AND THE EQUIPMENT GROUNDING CONDUCTOR FOR THE BOX WAS NOT CONTINUOUS. THIS ENERGIZED THE BOX, RESULTING IN THE EMPLOYEE'S ELECTROCUTION WHEN HE TOUCHED THE BOX WITH HIS BARE HAND.
Keywords: ELECTRICAL, ELECTROCUTED, ELECTRICAL WORK, GROUND FAULT, EQUIPMENT GROUNDING
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 781526 | Fatality | Electric Shock | Occupation not reported |
Translate