Inspection: 3350295 - Pepco

Inspection Information - Office: Va-E-Manassas (Regional Office)- Safety 0355114

 

Inspection Nr: 3350295
Report ID: 0355114
Date Opened: 01/30/1986

Site Address:
Pepco
1845 North Fort Meyer Drive
Arlington, VA 22209

Mailing Address:
1900 Pennsylvania Avenue, Washington, DC 20068

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 01/30/1986

Emphasis:

Case Closed: 06/16/1986


Related Activity
Type Activity Nr Safety Health
Referral 900635079 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations
Initial Penalty $480 $0 $0 $0 $0 $480
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100145 C02 I 03/14/1986 03/24/1986 $480 $480 $0 A - Amendment Citation has been deleted.

Investigation Summary

Investigation Nr: 694190
Event: 01/30/1986
BURN - ELECTRICAL FAULT IN TESTING EQUIPMENT

Two power line workers were checking the phasing of some splices they had made. They were using an Allis-Chalmers, Type F, 13.8-kilovolt, 1200-ampere, ground and test device. This particular device had a 3-millimeter-thick steel face. They were also using an A. B. Chance Company phasing tool (Catalogue No. 1876). The phasing tool had 178-millimeter-long probes screwed into its end. The probes were too long for the purpose, and an electric arc formed between the probes and the metal face of the ground and test device. Both employees were burned by the arc and were hospitalized for their injuries.

Keywords: BURN, ELECTRIC ARC, ELECTRICAL, POWER LINE WORKER, ELECTRICAL TESTING, TEST EQUIPMENT, E PTD, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 3350295 Hospitalized injury Other Electrical power installers and repairers
2 3350295 Hospitalized injury Other Electricians' apprentices
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.