Powered by GoogleTranslate

Inspection Detail

Inspection: 3342938 - Virginia Power

Inspection Information - Office: Va-E-Manassas (Regional Office)- Safety 0355114

 

Inspection Nr: 3342938
Report ID: 0355114
Date Opened: 09/17/1987

Site Address:
Virginia Power
Annadale Road & Clearview Drive
Falls Church, VA 22042

Mailing Address:
James River Plaza, Richmond, VA 23261

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/17/1987

Emphasis:

Case Closed: 02/16/1988


Related Activity
Type Activity Nr Safety Health
Accident 360632962

Investigation Summary

Investigation Nr: 14289334
Event: 08/24/1987
ELECTRIC SHOCK, BURNS, AND FALL - CONTACT WITH ENERGIZED BUS

A THREE-MAN, SUBSTATION MAINTENANCE CREW WAS REPLACING A WORN 15-KILOVOLT, 600-AMPERE ELECTRIC DISCONNECT SWITCH. THEY HAD BEEN THOROUGHLY BRIEFED BY THEIR SUPERVISOR ON THE CORRECT PROCEDURES TO ACCOMPLISH THE TASK. THE POWER HAD BEEN SWITCHED FROM THE WORN DISCONNECT AREA TO THE TRANSFER BUS SO THEY COULD DO THE WORK SAFELY. GROUNDS HAD BEEN INSTALLED AND ALL LADDERS HAD BEEN SECURED. ONE OF THE EMPLOYEES HAD HIS LADDER BETWEEN THE FIRST TWO DISCONNECT SWITCHES. HE WAS TO DISCONNECT THE LEADS FROM THESE TWO SWITCHES, THEN MOVE HIS LADDER TO HIS LEFT NEAR THE THIRD SWITCH, AND THEN CLIMB UP AND REMOVE THE LEADS. WHEN HE FINISHED THE FIRST TWO DISCONNECTS, HE CLIMBED UP ON THE STEEL, INSTEAD OF MOVING HIS LADDER, TO REMOVE THE THIRD SWITCH. IN SO DOING, THE BACK OF HIS SHOULDERS CONTACTED THE 7200-VOLT TRANSFER BUS AND KNOCKED HIM TO THE GROUND, A DISTANCE OF ABOUT 17 FEET. HE SUFFERED SEVERE ELECTRICAL BURNS AND VARIOUS CONTUSIONS AND ABRASIONS FROM THE FALL. HE LATER DIED AS A RESULT OF HIS INJURIES.

Keywords: BURN, ELECTRICAL, ELECTRIC SWITCH, LADDER, BUSBAR, E PTD, SUBSTATION, ELEC UTILITY WORK, ELECTRIC SHOCK, FALL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 3342938 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.