Inspection Detail
Inspection: 3326337 - Pargas Of Suburban Propane Gas Corporation
Inspection Information - Office: Va-E-Manassas (Regional Office)- Safety 0355114
Site Address:
Pargas Of Suburban Propane Gas Corporation
11221 Fairfax Station Road, Box 105
Fairfax Station, VA 22039
Mailing Address:
P. O. Box 129, 14111 John Marshall Highway, Gainesville, VA 22065
Union Status: NonUnion
SIC:5984
NAICS: 0
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/30/1986
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 10/09/1986
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Referral | 900811035 | Yes |
Investigation Summary
AT APPROXIMATELY 2:30 PM ON JULY 28, 1986, EMPLOYEES #1 AND #2 WERE FILLING 33.5 LP GAS CYLINDERS IN THE FILL ROOM OF AN LP GAS DISTRIBUTION PLANT. THE CYLINDERS WERE SET ON SCALES SO THAT THE EMPLOYEES COULD TELL WHEN THE TANKS WERE FULL. THE FILL AREA CONTAINED 3 SCALES, SIDE BY SIDE. ONLY THE LEFT AND RIGHT ONES WERE IN USE. THE TANK (CYLINDER) ON THE LEFT SCALE WAS CONNECTED AND BEING FILLED. AN EMPTY TANK HAD JUST BEEN PLACED ON THE RIGHT SCALE. THE FILLING GUN WAS HOOKED TO THE TANK, BUT THERE WAS NOT A GOOD FIT. PROPANE WAS LEAKING. EMPLOYEE #1 DISCONNECTED THE GUN TO READJUST THE FIT. THE TANK CHECK VALVE FAILED, ALLOWING A RAPID ESCAPE OF GAS. AS EMPLOYEE #1 ATTEMPTED TO REATTACH THE FILL GUN, A STATIC CHARGE WAS APPARENTLY CREATED BY THE RAPID ESCAPE OF GAS UNDER PRESSURE. A FLASH FIRE RESULTED, CAUSING BURNS TO THE FACE, HANDS AND ARMS OF BOTH EMPLOYEES. THEY WERE HOSPITALIZED.
Keywords: BURN, STATIC ELECTRICITY, CHECK VALVE, FLAMMABLE VAPORS, FIRE, LP GAS, GAS LEAK, ARM, FACE, HAND
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 3326337 | Hospitalized injury | Burn/Scald(Heat) | Motor transportation occuputions n.e.c. | ||
| 2 | 3326337 | Hospitalized injury | Burn/Scald(Heat) | Production helpers |
Translate