Powered by GoogleTranslate

Inspection Detail

Inspection: 3270683 - Wasatch-Dynalectric

Inspection Information - Office: Utah Division Of Occupational Safety And Health

 

Inspection Nr: 3270683
Report ID: 0854910
Date Opened: 06/05/1985

Site Address:
Wasatch-Dynalectric
6069 South Highland Drive
Salt Lake City, UT 84121

Mailing Address:
1574 South West Temple P O Box 26588, Salt Lake City, UT 84126

Union Status: Union

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/07/1985

Emphasis:

Case Closed: 07/01/2016


Related Activity
Type Activity Nr Safety Health
Accident 360780027
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $420 $0 $0 $0 $0 $420
Current Penalty $420 $0 $0 $0 $0 $420
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 359000501 07/03/1985 06/05/1985 $420 $420 $0 -  

Investigation Summary

Investigation Nr: 14456867
Event: 06/05/1985
BURN - ARCING CAUSED BY ELECTRICAL FAULT

AN EMPLOYEE WAS WORKING FROM AN AERIAL LIFT INSTALLING A JUMPER WIRE ON A 7200-VOLT OVERHEAD POWER LINE. THE AERIAL LIFT HAD BEEN RAISED SO THAT A METAL PART OF THE LIFT WAS TOUCHING THE NEUTRAL CONDUCTOR ON THE POLE. THE EMPLOYEE WAS HOLDING AN 8-FOOT HOT STICK WITH ONE END OF THE 44-INCH JUMPER WIRE ATTACHED. THE EMPLOYEE RAISED THE HOT STICK UNTIL IT CONTACTED ONE OF THE ENERGIZED PHASE CONDUCTORS ON THE POLE. THE OTHER (FREE) END OF THE JUMPER WIRE TOUCHED THE METAL POLE CLAMP ON THE AERIAL LIFT. THIS CAUSED A DIRECT FAULT TO THE NEUTRAL. THE EMPLOYEE RECEIVED BURNS ON HIS ARM AND ABDOMEN FROM THE RESULTING ELECTRIC ARC. THE EMPLOYEE WAS TREATED AT A LOCAL HOSPITAL AND RELEASED.

Keywords: BURN, CLOTHING, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRICAL FAULT, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 3270683 Non Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close