Inspection: 316720770 - Porterville Unified School District

Inspection Information - Office: Fresno District Office

 

Inspection Nr: 316720770
Report ID: 0950625
Date Opened: 11/20/2012

Site Address:
Porterville Unified School District
900 W. Pioneer Ave.
Porterville, CA 93257

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:9411

NAICS: 923110/Administration of Education Programs


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Health

Close Conference: 12/20/2012

Emphasis:

Case Closed: 01/29/2013


Related Activity
Type Activity Nr Safety Health
Accident 101088201

Investigation Summary

Investigation Nr: 201497294
Event: 11/20/2012
Refrigerant Leak Sends 16 School Workers to Hospital

On November 29, 2012, Employee #1, a 27-year-old male, Employee #2, a 26-year-old male, Employee #3, a 44-year-old female Employee #4, a 45-year-old female, Employee #5, a 53-year-old female, Employee #6, a 54-year-old female, Employee #7, a 41-year-old male, Employee #8, a 57-year-old male, Employee #9, a 65-year-old female, Employee #10, a 59 -year-old female, Employee #11, a 41-year-old female, Employee #12, a 51-year-old female, Employee #13, a 54-year-old female, Employee #14, a 49-year-old female, Employee #15, a 42-year-old female and Employee # 16, a 45-year-old female with Porterville Unified School District were involved in a catastrophic event causing the sixteen employees to be transported to three medical facilities after the release of three hundred pounds of R-507 refrigerant was released into Porterville Unified School District's Central Kitchen. The release occurred in the kitchen 47,000 cu. ft. cold room when the facility was not occupied. At first, Employee's entering the cold room did not detect or notice anything wrong, however as the refrigerant migrated from the cold room into the warmer cooking area, it expanded and filled the kitchen. Employee's in these warmer areas were able to detect a sweet smell and then began experiencing upper respiratory and eye irritations, which triggered an evacuation of the facility. The refrigerant release was found to be the failure of the air handler's evaporator coil that was abraded by an electrical conduit rubbing against it. During the installation of the air handler a hold-down clip that secures the conduit was not installed and the defect occurred under a cover that normally would not be removed for normal maintenance.

Keywords: EYE, LEAK, RESPIRATORY, GAS, REFRIGERANT, RESPIRATORY TRACT, CHEMICAL VAPOR, CHEMICAL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 316720770 Non Hospitalized injury Asphyxia Occupation not reported
2 316720770 Non Hospitalized injury Asphyxia Food batchmakers
3 316720770 Non Hospitalized injury Asphyxia Food batchmakers
4 316720770 Non Hospitalized injury Asphyxia Food batchmakers
5 316720770 Non Hospitalized injury Asphyxia Food batchmakers
6 316720770 Non Hospitalized injury Asphyxia Food batchmakers
7 316720770 Non Hospitalized injury Asphyxia Occupation not reported
8 316720770 Non Hospitalized injury Asphyxia Food batchmakers
9 316720770 Non Hospitalized injury Asphyxia Food batchmakers
10 316720770 Non Hospitalized injury Asphyxia Food batchmakers
11 316720770 Non Hospitalized injury Asphyxia Food batchmakers
12 316720770 Non Hospitalized injury Asphyxia Food batchmakers
13 316720770 Non Hospitalized injury Asphyxia Occupation not reported
14 316720770 Non Hospitalized injury Asphyxia Occupation not reported
15 316720770 Non Hospitalized injury Asphyxia Occupation not reported
16 316720770 Non Hospitalized injury Asphyxia Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.