Powered by GoogleTranslate

Inspection Detail

Inspection: 316270206 - Siemens Industry Inc

Inspection Information - Office: Hi-E-Honolulu

 

Inspection Nr: 316270206
Report ID: 0951510
Date Opened: 04/29/2013

Site Address:
Siemens Industry Inc
Olaa No. 6 Well
Mountain View, HI 96771

Mailing Address:
3333 Old Milton Pkwy, Alpharetta, GA 30005

Union Status: NonUnion

SIC:3823

NAICS: 334513/ Instruments and Related Products Manufacturing for Measuring, Displaying, and Controlling Industrial Process Variables


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/21/2013

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 08/12/2014


Related Activity
Type Activity Nr Safety Health
Accident 101951531
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $6,930 $0 $0 $0 $0 $6,930
Current Penalty $6,930 $0 $0 $0 $0 $6,930
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01002 Serious 19100333 B02 10/24/2013 11/18/2013 $6,930 $6,930 $0 11/15/2013 F - Formal Settlement  

Investigation Summary

Investigation Nr: 201943099
Event: 04/25/2013
Three Employee Receive Electric Shock, One Is Electrocuted

At approximately 9:15 a.m. on April 25, 2013, Employee #1, #2, and #3 were preparing for a scheduled test of a motor controller (MC) starter system in the control building of a water supply deep well and reservoir facility. The MC was a Series 81000 motor controller manufactured by Siemens Industry Inc. that would serve a 600 hp submersible pump, operating on 3-phase, 4,160 volt electric power. The pump was to be installed in the well at the site. Employee #1 was a senior engineer working for the Siemens. He was the primary designer of the Series 81000 and had 20 years of experience with similar equipment. Employee #2 was a design engineer for Phasetronics LLC, which manufactured a motor starter that was incorporated in the Siemens motor controller starter system. Employee #3 was the sole proprietor of Scada & Control Systems LLC, which had purchased and provided the electronic and control systems equipment for the deep well and reservoir facility. Employee #1 and #2 arrived at the facility with Employee #3 earlier in the week to troubleshoot and repair the MC starter system, which had failed during initial testing in August 2012. The MC system was in a metal cabinet in one of two banks of cabinets that faced each other 6.58 ft apart inside the control building. The door of the MC cabinet was approximately 90 in. high and 36 in. wide. The interior of the cabinet was divided into three physically separate compartments from top to bottom with the 120 volt MC system control panel in the middle compartment. The bottom compartment contained various wiring, leads for the three phases of the pump motor and a movable carriage that held contactors, fuses and other circuit parts for the pump motor and the MC control panel. The carriage was 18 in. wide. It fit on a track on the right side of the bottom compartment and occupied slightly over half of the compartment's 35 in. interior width. It was racked (moved forward or back) by a lever next to the cabinet door on the lower right side. At its rearmost position, the contactors engaged the main busbar and energized the system at 4,160 volts. This was stepped down to 120 volts for the control panel. An interlock inside the cabinet was designed to accept a tab on the cabinet door so that the lever could not be moved to rack the contactors if the door were open. With the carriage removed from the cabinet and the system de-energized, Employee #1 installed a monitoring instrument behind the control panel and attached a cable from it to one of the motor leads at the left rear of the bottom section. He and Employee #3 then placed the contactor carriage back on its track. Employee #1 knelt on the concrete floor in front of the open cabinet and used a screwdriver to defeat the interlock. He told Employee #3 to slowly raise the lever to rack the contactor (which would engage the busbar) while he watched to see that the carriage did not pinch the instrument cable. Employee #2 stood a few feet away by the opposite bank of cabinets preparing a laptop computer to monitor the system test. None of them was wearing any form of electrical protective equipment, such as insulated gloves or gauntlets, face shield, or flame resistant clothing. After the contactor was racked, which energized the exposed parts on the carriage at 4,160 volts, Employee #1 said the cable "looked okay." As Employee #2 and #3 turned away, Employee #1 reached with his left arm into the cabinet and his forearm contacted one of the energized parts on the carriage. Employee #3 saw Employee #1's body shaking and tried to pull him away from the cabinet while he threw the lever to rack out the contactor. In the process, he received an electric shock. Employee #2 was also shocked when his left arm touched the open cabinet door as he also tried to pull Employee #1 away. Employee #2 threw the main breaker for the building, which was roughly 12 ft to the left of the MC cabinet. He and Employee #3 pulled Employee #1 out of the cabinet and onto hi

Keywords: BURN, INSTALLING, PPE, ELECTRICAL TESTING, ELECTROCUTED, STRUCK AGAINST, ELEC CIRC PART--MISC, ELECTRIC SHOCK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 316270206 Fatality Electric Shock Electrical and electronic engineers
2 316270206 Non Hospitalized injury Electric Shock Electrical and electronic engineers
3 316270206 Non Hospitalized injury Electric Shock Electrical and electronic engineers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.