Inspection Detail
Inspection: 315533554 - B 2 Sales, Inc
Inspection Information - Office: Santa Ana District Office
Site Address:
B 2 Sales, Inc
233 E Bristol Lane
Orange, CA 92865
Mailing Address:
1101 E Truslow, Fullerton, CA 92831
Union Status: NonUnion
SIC:8711
NAICS: 541330/Engineering Services
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/07/2013
Emphasis:
Case Closed: 11/21/2013
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 102848884 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 2 | ||||
| Current Violations | 2 | 2 | ||||
| Initial Penalty | $0 | $0 | $0 | $6,200 | $0 | $6,200 |
| Current Penalty | $0 | $0 | $0 | $6,200 | $0 | $6,200 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 342 A | 10/09/2013 | 10/14/2013 | $5,000 | $5,000 | $0 | - | ||
| 2. | 01002 | Other | 23200002 A05 | 10/09/2013 | 10/14/2013 | $1,200 | $1,200 | $0 | - |
Investigation Summary
On May 1, 2013, the employer reported an industrial incident that had initially occurred on April 13, 2013 that later developed into a serious injury on April 22, 2013, when Employee #1 received skin grafts on the hand that was injured. On April 13, 2013, Employee #1, a 64-year-old male electrical engineering and testing technician with B 2 Sales Inc, was installing a 10 in. by 14 in. 12-gauge metal plate on the inside wall of a partially de-energized electrical panel so that a custom meter could be installed for the client. The load side of the panel was separated from the line side with a physical barrier and the main breaker switch was off such that the load side where the plate was to be installed was de-energized. Employee #1 was accompanied by another coworker who was being trained and also by a licensed electrician who had de-energized the line side of the 480-volt panel so that the plate and custom meter could be installed. Employee #1 verified that the power was off and proceeded to install the metal plate onto the inside wall of the panel. As Employee #1 was positioning the plate it into place, it dropped out of his hand and fell against the back side of the panel where it came into contact with the energized buss behind the barrier causing a short and a flash. Employee #1 sustained first and second degree burns to his right hand and forearm and a first degree burn to his cheek and forehead. Employee #1 was treated at an outpatient facility and on April 22, 2013 underwent skin graft surgery on his right hand.
Keywords: BURN, ELECTRIC ARC, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC, SKIN, ELECTRICAL BOX, FACE, HAND
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 315533554 | Non Hospitalized injury | Electric Shock | Electrical and electronic engineers |