Powered by GoogleTranslate

Inspection Detail

Inspection: 315533547 - Z Power & Distribution

Inspection Information - Office: Santa Ana District Office

 

Inspection Nr: 315533547
Report ID: 0950631
Date Opened: 05/31/2013

Site Address:
Z Power & Distribution
233 E Bristol Lane
Orange, CA 92865

Mailing Address:
1350 S Claudina, Anaheim, CA 92805

Union Status: NonUnion

SIC:3612

NAICS: 335311/ Power, Distribution, and Specialty Transformer Manufacturing


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/09/2013

Emphasis:

Case Closed: 10/10/2013


Related Activity
Type Activity Nr Safety Health
Accident 102848876

Investigation Summary

Investigation Nr: 202556650
Event: 04/13/2013
Employee Suffers Burns from Arc Flash Explosion

On April 13, 2013, an incident occurred as Employee #1 was installing a gauge metal plate on the inside wall of a partially deenergized electrical panel so that a custom meter could be installed for the client. The load side of the panel was separated from the line side with a physical barrier and the main breaker switch was off such that the load side where the plate was to be installed was deenergized. Employee #1 was standing behind his coworker and was observing the installation as training for future installations. The coworker verified that the power was off in the portion where he would be working and proceeded to install the metal plate onto the inside wall of the panel. As he was positioning the plate it into place, it dropped out of his hand and fell against the back side of the panel where it came into contact with the energized buss behind the barrier causing a short and a flash. Employee #1 sustained first and second degree burns to his face and head and received treatment the same day at an outpatient facility.

Keywords: BURN, HEAD, BUSBAR, HEALTH CARE FACILITY, TEST EQUIPMENT, BREAKER PLATE, FACE, HAND

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 315533547 Non Hospitalized injury Burn/Scald(Heat) Electrical and electronic technicians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close