Inspection Detail
Inspection: 315298091 - Nardone Electrical Corporation
Inspection Information - Office: Boston North Area Office
Site Address:
Nardone Electrical Corporation
Hanscom Airforce Base, Building 1435
Bedford, MA 01730
Mailing Address:
100 Winchester Street, Medford, MA 02155
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Complaint
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 03/01/2011
Emphasis: S:Commercial Constr, S:Electrical
Case Closed: 08/23/2011
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Complaint | 207859307 | Yes |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 3 | ||||
| Current Violations | 2 | 1 | 3 | |||
| Initial Penalty | $16,170 | $0 | $0 | $0 | $0 | $16,170 |
| Current Penalty | $7,000 | $0 | $0 | $2,600 | $0 | $9,600 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 19260095 A | 07/27/2011 | 08/02/2011 | $2,600 | $5,390 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Serious | 19260416 A01 | 07/27/2011 | 08/01/2011 | $3,500 | $5,390 | $0 | I - Informal Settlement | ||
| 3. | 01003 | Serious | 19260416 A03 | 07/27/2011 | 08/01/2011 | $3,500 | $5,390 | $0 | I - Informal Settlement |
Investigation Summary
On February 5, 2011, Employee # 1 and Employee # 2 were employed by Nardone Electrics. Employee # 1 and Employee # 2 were installing a replacement of an Automatic Transfer Switch (ATS) and related components for a building Uninterrupted Power Supply (UPS). The generator system failed which led to a transfer of building power to the UPS. Employee # 1 and Employee # 2 installed temporary wiring (welding leads) to bypass the ATS to provide continued power to the computer systems. After the workers completed the ATS replacement they turned the main switch on the Main Service Switch (MSS) panel to OFF and begin pulling the three phase permanent wiring into this cabinet. The grounding wire came in contact with energized 480 volt bus bars behind and above the main switch causing an arc flash. Employee # 1 and Employee # 2 sustained electrical burns.
Keywords: ELECTRIC ARC, ELECTRICIAN
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 315298091 | Hospitalized injury | Burn/Scald(Heat) | Occupation not reported | ||
| 2 | 315298091 | Hospitalized injury | Burn/Scald(Heat) | Occupation not reported |
Translate