Inspection Detail
Inspection: 315287995 - Faith Technologies Inc
Inspection Information - Office: Appleton Area Office
Site Address:
Faith Technologies Inc
2950 N Victory Ln
Appleton, WI 54914
Mailing Address:
Po Box 260, Menasha, WI 54952
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 04/15/2011
Emphasis: S:Electrical
Case Closed: 05/24/2011
Type | Activity Nr | Safety | Health |
---|---|---|---|
Referral | 200652949 | Yes |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $7,000 | $0 | $0 | $0 | $0 | $7,000 |
Current Penalty | $7,000 | $0 | $0 | $0 | $0 | $7,000 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19260416 A03 | 04/27/2011 | 05/02/2011 | $7,000 | $7,000 | $0 | - |
Investigation Summary
A foreman and an electrician's helper were assigned to remove a temporary electrical service from a construction site. A permanent 480-volt transformer on the site supplied the temporary service. When the employees arrived at the temporary service, they saw that the meter had been pulled and an insulated cover was over the contacts, with a seal on the meter box. The foreman opened an electrical box adjacent to the meter. This box enclosed the main disconnect for the feeder from the transformer to the meter. The foreman watched as the helper tested the feeder. The feeder from the disconnect was deenergized on the load side of the disconnect. The foreman told the helper that he could disconnect the temporary service, and the foreman left the immediate area. The helper cut the feeder on the supply side of the disconnect, which was still energized, and caused an electrical fault. The ensuing electric arc threw the helper about a meter back and ignited his clothing. The employee received first- and second-degree burns on the front midsection of his body and on small areas on his face. He was hospitalized at a burn center for his injuries. He was released as an outpatient several days later.
Keywords: BURN, CLOTHING, ELECTRIC ARC, ELECTRICAL, ELECTRICAL WORK, LOCKOUT, E C, ELECTRICAL FAULT, UNTRAINED
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 315287995 | Hospitalized injury | Burn/Scald(Heat) | Helpers, construction trades |